| General specifications | ||
|---|---|---|
| Number of pins | 6 | |
| Electrical specifications | ||
| Rated voltage | 160 V | |
| Rated current | 8 A | |
| Mechanical specifications | ||
| Core cross-section | 0.14 ... 1.5 mm2 | |
| Housing | blue | |
| Mass | approx. 5 g | |
| Dimensions | (W x H x D) 33.3 mm x 12.4 mm x 20.8 mm | |
| Construction type | spring terminal | |
| General specifications | ||
|---|---|---|
| Number of pins | 6 | |
| Electrical specifications | ||
| Rated voltage | 160 V | |
| Rated current | 8 A | |
| Mechanical specifications | ||
| Core cross-section | 0.14 ... 1.5 mm2 | |
| Housing | blue | |
| Mass | approx. 5 g | |
| Dimensions | (W x H x D) 33.3 mm x 12.4 mm x 20.8 mm | |
| Construction type | spring terminal | |
| Описание оборудования | ||
|---|---|---|
| Fieldbus Diagnostic Handheld | ||
| Supply | ||
|---|---|---|
| Rated voltage | 19.2 ... 35 V DC | |
| Rated current | 150 ... 100 mA | |
| Power dissipation | 3 W | |
| Ethernet Interface | ||
| Intrinsically safe port | 10 BASE-T/100 BASE-TX | |
| Non-intrinsically safe port | 10 BASE-T/100 BASE-TX | |
| Connection type | 2 x RJ-45 , IEC 60603-7 | |
| Connector pinout | socket TIA/EIA-568-B | |
| Transfer rate | 10/100 Mbit/s , Auto-Negotiation | |
| Operating mode | Half/Full Duplex | |
| Cable type | CAT5e S/FTP AWG 24, Installation cable, L/R ratio max. 10 µH/&Omega of all strand combinations | |
| I.S. cable length | typ. 100 m/20 °C | |
| Total cable length | typ. 200 m/20 °C | |
| Number of isolators | max. 2 in series connection | |
| Indicators/operating means | ||
| LED PWR | green: Power on | |
| LED ACT | yellow: communication active | |
| LED 10/100 | yellow ON: Transfer rate 100 MBit/s , OFF: 10 MBit/s | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Standard conformity | ||
| Galvanic isolation | EN 50020 | |
| Degree of protection | IEC 60529 | |
| Climatic conditions | DIN IEC 721 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ethernet | IEEE 802.3 , IEEE 802.3u | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | &le 95 % non-condensing | |
| Shock resistance | 15 g 11 ms | |
| Vibration resistance | 1 g 10 ... 150 Hz | |
| Pollution degree | max. 2, according to IEC 60664 | |
| Mechanical specifications | ||
| Connection type | Terminals | |
| Core cross-section | up to 2.5 mm2 | |
| Housing material | Polyamide PA 66 | |
| Degree of protection | IP20 according to EN 60529 | |
| Mass | 195 g | |
| Mounting | DIN rail mounting | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 07 ATEX 2025 X | |
| Marking | II (1) G [Ex ia Ga] IIB , II (1) D [Ex ia Da] IIIC , II 3(1)G Ex nA [ia Ga] IIB T4 Gc II 3 (1D) G Ex nA [ia IIIC Da] IIB T4 Gc I (M1) [Ex ia Ma] I | |
| Supply | ||
| Maximum safe voltage | 253 V AC | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| CSA approval | CSA 15.70016295 | |
| Control drawing | 116-B032 | |
| Approved for | Class I, Zone 2, AEx/Ex nA [ia Ga] IIB T4 Gc Class I, Zone 2, AEx/Ex nA [ia Da IIIC] IIB T4 Gc | |
| IECEx approval | IECEx PTB 09.0053X | |
| Approved for | [Ex ia Ga] IIB [Ex ia Da] IIIC Ex nA [ia Ga] IIB T4 Gc Ex nA [ia IIIC Da] IIB T4 Gc [Ex ia Ma] I | |
| Certificates and approvals | ||
| Patents | This product may be covered by the following patent: US7,687,791 | |
| General specifications | ||
|---|---|---|
| Design / Mounting | Outside installation | |
| Installed components | Binary multi-input/output R8D0-MIO-Ex12.FF* , For technical data on installed electronic component see data sheet. | |
| Fieldbus interface | ||
| Fieldbus type | FOUNDATION Fieldbus | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation | |
| Mechanical specifications | ||
| Degree of protection | IP66 | |
| Dimensions | (W x H x D) 271 x 271 x 136 mm | |
| Mounting | thru-holes Ø6.5 mm | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 07 ATEX 1061 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
| Certificate | PF 16 CERT 4011 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
| Marking | II 3(1)G Ex ic [ia Ga] IIC T4 Gc II 3(1)G Ex ec [ia Ga] IIC T4 Gc II 3(1)D Ex tc [ia Da] IIIC T135°C Dc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-31:2014 | |
| International approvals | ||
| IECEx approval | IECEx PTB 07.0036 , Zone 1 , suitable Junction Box on request IECEx PTB 09.0016 , Zone 2 , suitable Junction Box on request | |
| INMETRO | TÜV 13.1143 | |
| General specifications | ||
|---|---|---|
| Design / Mounting | Outside installation | |
| Installed components | Binary multi-input/output R8D0-MIO-Ex12.PA* , For technical data on installed electronic component see data sheet. | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS PA | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation | |
| Mechanical specifications | ||
| Degree of protection | IP66 | |
| Dimensions | (W x H x D) 271 x 271 x 136 mm | |
| Mounting | thru-holes Ø6.5 mm | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 07 ATEX 1061 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
| Certificate | PF 16 CERT 4011 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
| Marking | II 3(1)G Ex ic [ia Ga] IIC T4 Gc II 3(1)G Ex ec [ia Ga] IIC T4 Gc II 3(1)D Ex tc [ia Da] IIIC T135°C Dc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-31:2014 | |
| International approvals | ||
| IECEx approval | IECEx PTB 07.0036 , Zone 1 , suitable Junction Box on request IECEx PTB 09.0016 , Zone 2 , suitable Junction Box on request | |
| INMETRO | TÜV 13.1143 | |
| Supply | ||
|---|---|---|
| Connection | backplane bus | |
| Rated voltage | 5 V DC , only in connection with the power supplies FB92** | |
| Power consumption | 2 W | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS DP/DP-V1 | |
| PROFIBUS DP | ||
| Connection | wired to Ex e terminals via backplane | |
| Baud rate | up to 1.5 MBit/s | |
| Protocol | PROFIBUS DP/DP V1 read/write services | |
| Number of stations per bus line | max. 125 (PROFIBUS), max. 119 (service bus) | |
| Cyclic process data | 240 bytes input and (simultaneously) 240 bytes output | |
| Number of stations per bus segment | max. 31 (RS-485 standard) | |
| Number of repeaters between Master and Slave | max. 3 | |
| Supported I/O modules | all FB remote I/O modules | |
| Bus length | max. 1000 m (FOL, 1.5 MBaud), max. 1000 m (copper cable, 187.5 kBd), max. 200 m (copper cable, 1.5 MBd) | |
| Addressing | via configuration software | |
| PROFIBUS address | 0 ... 126 (factory standard setting: 126) | |
| GSE file | CGV61711.gsd/gse | |
| HART communication | via PROFIBUS or service bus | |
| Internal bus | ||
| Connection | backplane bus | |
| Redundancy | via front connector | |
| Indicators/settings | ||
| LED indicator | LED green (power supply): On = operating, fast flash = cold start LED red (collective alarm): On = internal fault, flashing = no PROFIBUS connection LED yellow (operating mode): flashing 1 (1:1 ratio) = active, normal operation flashing 2 (7:1 ratio) = active, simulation | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative humidity | 95 % non-condensing | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
| Connection | via backplane | |
| Mass | approx. 750 g | |
| Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 97 ATEX 1074 U | |
| Marking | II 2(1) G Ex d [ia Ga] IIC Gb | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 | |
| International approvals | ||
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Supply | ||
|---|---|---|
| Connection | backplane bus | |
| Rated voltage | 5 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 2 W | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS DP/DP-V1 | |
| PROFIBUS DP | ||
| Connection | 9-pin Sub-D socket via backplane | |
| Baud rate | up to 1.5 MBit/s | |
| Protocol | PROFIBUS DP/DP V1 read/write services | |
| Number of stations per bus line | max. 125 (PROFIBUS), max. 119 (service bus) | |
| Cyclic process data | 240 bytes input and (simultaneously) 240 bytes output | |
| Number of stations per bus segment | max. 31 (RS-485 standard) | |
| Number of repeaters between Master and Slave | max. 3 | |
| Supported I/O modules | all LB remote I/O modules | |
| Bus length | max. 1000 m (FOL, 1.5 MBaud), max. 1000 m (copper cable, 187.5 kBd), max. 200 m (copper cable, 1.5 MBd) | |
| Addressing | via configuration software | |
| PROFIBUS address | 0 ... 126 (factory standard setting: 126) | |
| GSE file | CGV61711.gsd/gse | |
| HART communication | via PROFIBUS or service bus | |
| Internal bus | ||
| Connection | backplane bus | |
| Redundancy | via backplane | |
| Indicators/settings | ||
| LED indicator | LED P: (power supply): On = operating, fast flash = cold start LED 1: (collective alarm): On = internal fault, flashing = no PROFIBUS connection LED 2: (status fieldbus): flashing = PROFIBUS receive channel active LED 3: (status service bus): flashing = service bus receive channel active LED 4: (operating mode): flashing 1 (1:1 ratio) = active, normal operation flashing 2 (7:1 ratio) = active, simulation LED 5: (status fieldbus): flashing = PROFIBUS response channel active LED 6: (status service bus): flashing = service bus response channel active | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , mounted on backplane | |
| Connection | via backplane | |
| Mass | approx. 120 g | |
| Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| UL approval | E106378 | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA IIC T4 Gc | |
| Marine approval | ||
| Bureau Veritas Marine | 22449/B0 BV | |
| Steckplätze | ||
|---|---|---|
| Buskoppler | 2 | |
| E/A-Module | >12, je nach Typ | |
| Versorgung | ||
| Anschluss | Anschluss an Ex-e-Klemmen über Backplane | |
| Sicherheitst. Maximalspannung Um | 253 V AC | |
| Eingangsspannungsbereich | 90 ... 253 V AC | |
| Verlustleistung | ca. 18 % der entnommenen Leistung | |
| Leistungsaufnahme | max. 47 W Parallelschaltung mit weiterem FB9215B2 (autom. Leistungsaufteilung) | |
| Einschaltstrom (< 2 ms) | 30 A max. (115 V AC) 50 A max. (230 V AC) | |
| Eingang | ||
| Eingangsfrequenz | 50 ... 60 Hz | |
| Ausgang | ||
| Spannung | 5,4 V DC +/- 5% , 12 V DC +/- 3% | |
| Leistung | P5V &le 5,4 W, P12V &le 39 W - P5V | |
| Anzeigen/Einstellungen | ||
| LED-Anzeige | LED grün: AUS bei Verlust der Netzspannung oder internen Spannungen (12 V, 5,4 V) | |
| Richtlinienkonformität | ||
| Elektromagnetische Verträglichkeit | ||
| Richtlinie 2014/30/EU | EN 61326-1:2013 | |
| Konformität | ||
| Elektromagnetische Verträglichkeit | NE 21:2007 | |
| Schutzart | IEC 60529:2000 | |
| Umgebungsbedingungen | ||
| Umgebungstemperatur | -20 ... 60 °C (-4 ... 140 °F) | |
| Lagertemperatur | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative Luftfeuchtigkeit | 95 % nicht kondensierend | |
| Schockfestigkeit | Schockform I, Schockdauer 11 ms, Schockamplitude 15 g, Anzahl der Schocks 18 | |
| Schwingungsfestigkeit | Frequenzbereich 10 ... 150 Hz Übergangsfrequenz: 57,56 Hz, Amplitude/Beschleunigung ± 0,075 mm/1 g 10 Zyklen Frequenzbereich 5 ... 100 Hz Übergangsfrequenz: 13,2 Hz Amplitude/Beschleunigung ± 1 mm/0,7 g 90 Minuten bei jeder Resonanz | |
| Schadgas | beständig in Umgebungsbedingungen nach ISA S71.04-1985, Severity Level G3 | |
| Mechanische Daten | ||
| Schutzart | IP20 (Modul) , separates Gehäuse entsprechend Systembeschreibung erforderlich | |
| Masse | ca. 890 g | |
| Abmessungen | 57 x 107 x 132 mm | |
| Daten für den Einsatz in Verbindung mit explosionsgefährdeten Bereichen | ||
| EU-Baumusterprüfbescheinigung | PTB 97 ATEX 1074 U | |
| Kennzeichnung | II 2 G Ex d IIC Gb | |
| Galvanische Trennung | ||
| Ausgang/Versorgung | EN 60950-1 (sicherheitstechnisch < 60 V, externe Stromversorgung SELV/PELV) | |
| Richtlinienkonformität | ||
| Richtlinie 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 | |
| Internationale Zulassungen | ||
| EAC-Zulassung | Russland: RU C-IT.MIII06.B.00129 | |
| Schiffsbau-Zulassung | ||
| Lloyd Register | 15/20021 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Steckplätze | ||
|---|---|---|
| Buskoppler | 2 | |
| E/A-Module | >12, je nach Typ | |
| Versorgung | ||
| Sicherheitst. Maximalspannung Um | 60 V DC (SELV/PELV) | |
| Eingangsspannungsbereich | 18 ... 32 V DC (SELV/PELV) | |
| Verlustleistung | ca. 15 % der entnommenen Leistung | |
| Leistungsaufnahme | max. 30 W für Zone-2-Anwendungen max. 45 W für Anwendungen im sicheren Bereich Parallelschaltung mit anderen LB9006C (autom. Leistungsaufteilung) | |
| Einschaltstrom | 1,5 A (10 ms) | |
| Ausgang | ||
| Spannung | 5,4 V DC +/- 5% , 12 V DC + 4/- 2% | |
| Leistung | P5V &le 5,4 W, P12V &le 25 W - P5V für Zone-2-Anwendungen P5V &le 5,4 W, P12V &le 39 W - P5V für Anwendungen im sicheren Bereich | |
| Anzeigen/Einstellungen | ||
| LED-Anzeige | Power-LED (P) grün: erlischt bei Ausfall der 24 V oder 12 V oder 5 V | |
| Richtlinienkonformität | ||
| Elektromagnetische Verträglichkeit | ||
| Richtlinie 2014/30/EU | EN 61326-1 | |
| Konformität | ||
| Elektromagnetische Verträglichkeit | NE 21 | |
| Schutzart | IEC 60529 | |
| Umgebungsbedingungen | ||
| Umgebungstemperatur | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (nicht-Ex) | |
| Lagertemperatur | -25 ... 85 °C (-13 ... 185 °F) | |
| Schockfestigkeit | Schockform I, Schockdauer 11 ms, Schockamplitude 15 g, Anzahl der Schocks 18 | |
| Schwingungsfestigkeit | Frequenzbereich 10 ... 150 Hz Übergangsfrequenz: 57,56 Hz, Amplitude/Beschleunigung ± 0,075 mm/1 g 10 Zyklen Frequenzbereich 5 ... 100 Hz Übergangsfrequenz: 13,2 Hz Amplitude/Beschleunigung ± 1 mm/0,7 g 90 Minuten bei jeder Resonanz | |
| Schadgas | beständig in Umgebungsbedingungen nach ISA S71.04-1985, Severity Level G3 | |
| Mechanische Daten | ||
| Schutzart | IP20 (Modul) , auf Backplane montiert | |
| Masse | ca. 220 g | |
| Abmessungen | 32,5 x 100 x 102 mm | |
| Daten für den Einsatz in Verbindung mit explosionsgefährdeten Bereichen | ||
| Zertifikat | PF 08 CERT 1234 X | |
| Kennzeichnung | II 3 G Ex nA IIC T4 Gc | |
| Galvanische Trennung | ||
| Ausgang/Versorgung, interner Bus | EN 60950-1 (Sicherheitsanforderung: < 60 V, externe Versorgung SELV/PELV) | |
| Richtlinienkonformität | ||
| Richtlinie 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| Internationale Zulassungen | ||
| UL-Zulassung | E106378 | |
| IECEx-Zulassung | BVS 09.0037X | |
| Zugelassen für | Ex nA IIC T4 Gc | |
| Schiffsbau-Zulassung | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 2 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
| Power dissipation | 1.5 W | |
| Power consumption | 3 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Analog input | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | pressure converter | |
| Field device [2] | flow converter | |
| Field device [3] | level converter | |
| Field device [4] | Temperature Converter | |
| Field device interface | ||
| Connection | 2-wire transmitter | |
| Connection [2] | 3-wire transmitter | |
| Connection [3] | 4-wire transmitter | |
| Connection | 2-wire transmitter (HART):Supply circuit: channel I 1+, 2-, channel II 5+, 6-, channel III 9+, 10-, channel IV 13+, 14-3-wire transmitter:Supply circuit: channel I 1+, 4-, channel II 5+, 8-, channel III 9+, 12-, channel IV 13+, 16-Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16-4-wire transmitter (powered externally):Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16- | |
| Transmitter supply voltage | min. 15 V at 20 mA 21.5 V at 4 mA | |
| Input resistance | 15 &Omega | |
| Conversion time | max. 100 ms | |
| Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
| Short-circuit | factory setting: > 22 mA configurable between 0 ... 26 mA | |
| Open-circuit | factory setting: < 1 mA configurable between 0 ... 26 mA | |
| HART communication | yes | |
| HART secondary variable | yes | |
| Transfer characteristics | ||
| Deviation | ||
| After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
| Resolution | 12 Bit (0 ... 26 mA) | |
| Refresh time | 100 ms | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2000 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative humidity | 95 % non-condensing | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
| Connection | Ex e spring terminal with protective cover | |
| Mass | approx. 750 g | |
| Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BVS 11 ATEX E 093 X | |
| Marking | II 2 G Ex db eb IIC T4 | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-7:2007 | |
| International approvals | ||
| ATEX approval | BVS 11 ATEX E 093X | |
| INMETRO | Brazil: TÜV 14.1599X | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power dissipation | 0.4 W | |
| Power consumption | 1 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Analog input | ||
| Number of channels | 1 | |
| Suitable field devices | ||
| Field device | pressure converter | |
| Field device [2] | flow converter | |
| Field device [3] | level converter | |
| Field device [4] | Temperature Converter | |
| Field device interface | ||
| Connection | 2-wire transmitter | |
| Connection [2] | 3-wire transmitter | |
| Connection [3] | 4-wire transmitter | |
| Connection | 2-wire transmitter (HART): supply circuit: 2/3+, 4/5- 3-wire transmitter (HART): supply circuit: 2/3+, 6- measuring circuit: 4/5+, 6- 4-wire transmitter (separately powered): measuring circuit: 4/5+, 6- HART measuring circuit: 1+, 6- | |
| Transmitter supply voltage | min. 15 V at 20 mA 21.5 V at 4 mA | |
| Input resistance | 15 &Omega (terminals 5, 6) 236 &Omega (terminals 1, 6) HART | |
| Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
| Short-circuit | factory setting: > 22 mA configurable between 0 ... 26 mA | |
| Open-circuit | factory setting: < 1 mA configurable between 0 ... 26 mA | |
| HART communication | yes | |
| HART secondary variable | yes | |
| Transfer characteristics | ||
| Deviation | ||
| After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
| Resolution | 12 Bit (0 ... 26 mA) | |
| Refresh time | 100 ms | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1) red: line fault (lead breakage or short circuit) Status LED (2) yellow: Live Zero monitoring | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2000 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 90 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Certificate | BVS 13 ATEX E 038 X | |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 EN 60079-11:2012 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | BVS 13 ATEX E 038X | |
| IECEx approval | BVS 13.0043X | |
| Approved for | Ex nA [ic] IIC T4 Gc | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power dissipation | 0.4 W | |
| Power consumption | 1 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Analog output | ||
| Number of channels | 1 | |
| Suitable field devices | ||
| Field device | Proportional Valve | |
| Field device [2] | I/P converters | |
| Field device [3] | on-site display | |
| Connection | channel I: 2/3+, 4/5- | |
| Current | 0 ... 25 mA short-circuit protected | |
| Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
| Short-circuit | factory setting: < 50 &Omega configurable between 0 ... 26 mA | |
| Open-circuit | deviation of preset output value > 0.5 mA | |
| Load | 750 &Omega max. | |
| HART communication | yes | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Transfer characteristics | ||
| Deviation | ||
| After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
| Refresh time | 100 ms | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1) red: line fault (lead breakage or short circuit) | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2000 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 90 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Certificate | BVS 12 ATEX E 115 X | |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc | |
| Galvanic isolation | ||
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | BVS 12 ATEX E 115 X | |
| IECEx approval | BVS 11.0068X | |
| Approved for | Ex nAc [ic] IIC T4 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
| Power consumption | 0.45 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Analog input | ||
| Number of channels | 1 | |
| Suitable field devices | ||
| Field device | voltage input | |
| Connection | voltage input: 5+, 6- | |
| Measurement range | 0 ... 10 V | |
| Smallest span | 500 mV | |
| Linearity error | 0.1 % | |
| Input resistance | 100 k&Omega | |
| Conversion time | max. 100 ms | |
| Indicators/settings | ||
| LED indicator | LED green: supply | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative humidity | 95 % non-condensing | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 350 g | |
| Dimensions | 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 97 ATEX 1074 U | |
| Marking | II 2(1) G Ex d [ia Ga] IIC Gb II (1) D [Ex ia Da] IIIC | |
| Input | ||
| Voltage | 0.9 V | |
| Current | 0.2 mA | |
| Power | 0.2 mW (linear characteristic) | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PTB 97 ATEX 1075 PTB 97 ATEX 1074 U | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 0.45 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Analog input | ||
| Number of channels | 1 | |
| Suitable field devices | ||
| Field device | voltage input | |
| Connection | voltage input: 5+, 6- | |
| Measurement range | 0 ... 10 V | |
| Smallest span | 500 mV | |
| Linearity error | 0.1 % | |
| Input resistance | 100 k&Omega | |
| Conversion time | max. 100 ms | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Status LED (1) red: line fault | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 90 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 03 ATEX 2042 | |
| Marking | II (1) G [Ex ia] IIC II (1) D [Ex ia] IIIC | |
| Input | ||
| Voltage | 0.9 V | |
| Current | 0.2 mA | |
| Power | 0.2 mW (linear characteristic) | |
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PTB 03 ATEX 2042 | |
| UL approval | E106378 | |
| Control drawing | 116-0322 | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 2 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
| Power consumption | 1.6 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital output | ||
| Number of channels | 2 | |
| Field device interface | ||
| Connection | Relay output | |
| Connection | channel I: 1-2 NO channel II: 3-4 NO channel III: 5-6 NO channel IV: 7-8 NO channel V: 9-10 NO channel VI: 11-12 NO channel VII: 13-14 NO channel VIII: 15-16 NO | |
| Relay | ||
| Switching voltage | 24 V DC / AC | |
| Switching current | 1 A DC / AC resistive load | |
| Switch power | 30 VA / 30 W | |
| Minimum load | 1 V 1 mA | |
| Electrical life | 0.1 mio. cycles | |
| Contact Material | AgPd gold plated | |
| Response time | 20 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: communication fault | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2000 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative humidity | 95 % non-condensing | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
| Connection | Ex e spring terminal with protective cover | |
| Mass | approx. 750 g | |
| Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BVS 11 ATEX E 093 X | |
| Marking | II 2 G Ex db eb IIC T4 | |
| Galvanic isolation | ||
| Output/power supply, internal bus | safe electrical isolation acc. to EN 61010-1:2010 | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-7:2007 | |
| International approvals | ||
| ATEX approval | BVS 11 ATEX E 093X | |
| INMETRO | Brazil: TÜV 14.1599X | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 2 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 1.2 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital output | ||
| Number of channels | 4 | |
| Field device interface | ||
| Connection | Relay output | |
| Connection | channel I: 1-2 NC, 3 channel II: 6-7 NC, 8 channel III: 9-10 NC, 11 channel IV: 14-15 NC, 16 | |
| Relay | ||
| Switching voltage | DC: 30 V AC: 150 V | |
| Switching current | 1 A DC / AC resistive load | |
| Switch power | DC: 30 W , AC: 60 W | |
| Minimum load | 1 V 1 A | |
| Electrical life | 0.1 mio. cycles | |
| Contact Material | AgPd gold plated | |
| Response time | 20 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Status LED (I) red: communication error | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Low voltage | ||
| Directive 2006/95/EC | EN 61010-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 130 g | |
| Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA nC IIC T4 Gc | |
| Galvanic isolation | ||
| Output/power supply, internal bus | safe electrical isolation acc. to EN 61010-1 | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| UL approval | E106378 | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ic] IIC T4 Gc | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 2 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
| Power consumption | 0.6 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| temperature input | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | resistance thermometer | |
| Field device [3] | slide-wire sensors | |
| Field device [5] | potentiometer | |
| Field device interface | ||
| Connection | 2-wire sensor | |
| Connection [2] | 3-wire sensor | |
| Connection [3] | 4-wire sensor | |
| Connection | channel I: resistance/potentiometer input 1 ... 4 channel II: resistance/potentiometer input 5 ... 8 channel III: resistance/potentiometer input 9 ... 12 channel IV: resistance/potentiometer input 13 ... 16 | |
| Measurement range | Pt100 (18-390 &Omega) (500 &Omega incl. line resistance) Pt200 (37-780 &Omega) Pt500 (92-1952 &Omega) Pt1000 (185-3905 &Omega) Ni100 (69-270 &Omega) Ni500 (345-1350 &Omega) Ni1000 (690-2700 &Omega) | |
| Slide-wire sensor | 0 ... 10 k&Omega | |
| Measuring current | 200 µA | |
| Smallest span | 50 &Omega for 0.1 % accuracy | |
| Linearity error | 0.1 % | |
| Conversion time | max. 500 ms (4 channels) max. 1 s (for 4x 3-wire Pt100) | |
| Busy after download | 5 ... 15 s | |
| Lead resistance | max. 50 &Omega per strand | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Short-circuit | < 10 &Omega | |
| Open-circuit | > 1 k&Omega | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault, collective alarm , flashing: communication error | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative humidity | 95 % non-condensing | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 750 g | |
| Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 97 ATEX 1074 U | |
| Marking | II 2(1) G Ex d [ia Ga] IIC Gb II (1) D [Ex ia Da] IIIC | |
| Input | ||
| Voltage | 7.14 V | |
| Current | 70 mA | |
| Power | 123 mW (linear characteristic) | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PTB 97 ATEX 1075 PTB 97 ATEX 1074 U | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 0.45 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| temperature input | ||
| Number of channels | 1 | |
| Suitable field devices | ||
| Field device | resistance thermometer | |
| Field device [3] | slide-wire sensors | |
| Field device interface | ||
| Connection | 2-wire sensor | |
| Connection [2] | 3-wire sensor | |
| Connection [3] | 4-wire sensor | |
| Connection | 2-wire connection: 5, 6 3-wire connection: 1, 5, 6 4-wire connection: 1, 2, 5, 6 | |
| Measurement range | 10 ... 400 &Omega (500 &Omega incl. line resistance) | |
| Slide-wire sensor | 10 ... 400 &Omega | |
| Measuring current | 200 µA | |
| Smallest span | 20 &Omega for 0.1 % accuracy | |
| Linearity error | 0.1 % | |
| Conversion time | max. 20 ms without LFD max. 150 ms with LFD | |
| Lead resistance | max. 50 &Omega per strand | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Short-circuit | < 10 &Omega | |
| Open-circuit | > 1 k&Omega | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Status LED (1) red: line fault | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 90 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ic] IIC T4 Gc | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 2 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
| Power consumption | 0.7 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Input | ||
| Digital signals (active) | ||
| Switching point: ON | ||
| Digital input | ||
| Number of channels | 8 | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection | channel I: 1+, 2- channel II: 3+, 4- channel III: 5+, 6- channel IV: 7+, 8- channel V: 9+, 10- channel VI: 11+, 12- channel VII: 13+, 14- channel VIII: 15+, 16- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 1 ms | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative humidity | 95 % non-condensing | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 750 g | |
| Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 97 ATEX 1074 U | |
| Marking | II 2(1) G Ex d [ia Ga] IIC Gb II (1) D [Ex ia Da] IIIC | |
| Input | ||
| Voltage | 14.9 V | |
| Current | 15.7 mA | |
| Power | 58.2 mW (linear characteristic) | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PTB 97 ATEX 1075 PTB 97 ATEX 1074 U | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 1.2 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 8 | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection | Terminals 1+, 2-, 3+, 4-, 5+, 6-, 7+, 8-, 9+, 10-, 11+, 12-, 13+,14-, 15+, 16- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 15 ms | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-8) red: line fault (lead breakage or short circuit) , yellow: signal (per channel) | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with spring terminal (0.14 ... 0.5 mm2) | |
| Mass | approx. 90 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | EXA 13 ATEX 0036X | |
| Marking | II 3(1) G Ex nA [ia Ga] IIC T4 Gc I (M1) [Ex ia Ma] I II (1) D [Ex ia Da] IIIC | |
| Input | ||
| Voltage | 10 V | |
| Current | 12 mA | |
| Power | 30 mW (linear characteristic) | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2011 EN 60079-11:2011 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | EXA 13 ATEX 0036X | |
| UL approval | E106378 | |
| IECEx approval | EXA 13.0003X | |
| Approved for | Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 2 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
| Power consumption | 2.2 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital output | ||
| Number of channels | 8 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 2- channel II: 3+, 4- channel III: 5+, 6- channel IV: 7+, 8- channel V: 9+, 10- channel VI: 11+, 12- channel VII: 13+, 14- channel VIII: 15+, 16- | |
| Current limit | 8 mA | |
| Open loop voltage | 20 V | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Test current | 0.33 mA | |
| Short-circuit | < 300 &Omega | |
| Open-circuit | > 50 k&Omega | |
| Response time | 20 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault , communication error red flashing | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative humidity | 95 % non-condensing | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 750 g | |
| Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 97 ATEX 1074 U | |
| Marking | II 2 G Ex d [ib] IIC Gb II (2) D [Ex ib Db] IIIC | |
| Galvanic isolation | ||
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PTB 97 ATEX 1075 PTB 97 ATEX 1074 U | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 2 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 2.2 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital output | ||
| Number of channels | 8 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 2- channel II: 3+, 4- channel III: 5+, 6- channel IV: 7+, 8- channel V: 9+, 10- channel VI: 11+, 12- channel VII: 13+, 14- channel VIII: 15+, 16- | |
| Current limit | 8 mA | |
| Open loop voltage | 20 V | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Test current | 0.33 mA | |
| Short-circuit | < 300 &Omega | |
| Open-circuit | > 50 k&Omega | |
| Response time | 20 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault , communication error red flashing | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 160 g | |
| Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 03 ATEX 2042 | |
| Marking | II (2) G [Ex ib] IIC II (2) D [Ex ib] IIIC | |
| Output | ||
| Voltage | 28 V | |
| Current | 13.5 mA | |
| Power | 376 mW (characteristic curve rectangular type) | |
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X PTB 03 ATEX 2042 | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ib Gb] IIC T4 Gc [Ex ib Db] IIIC | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
| Power consumption | 0.6 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 1 | |
| Function | ||
| Function | Counter  | |
| Function [2] | frequency | |
| Function [3] | direction of rotation | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection | channel I: 1+, 2/3- direction: 4+, 5/6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | in frequency + counter mode: 12.5 ms otherwise 20 µs | |
| Operating frequency | 0 ... 400 Hz in frequency + counter mode ... 40 Hz | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative humidity | 95 % non-condensing | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 350 g | |
| Dimensions | 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 97 ATEX 1074 U | |
| Marking | II 2(1) G Ex d [ia Ga] IIC Gb II (1) D [Ex ia Da] IIIC | |
| Input | ||
| Voltage | 10.5 V | |
| Current | 23.3 mA | |
| Power | 61.2 mW (linear characteristic) | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PTB 97 ATEX 1075 PTB 97 ATEX 1074 U | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 0.6 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 1 | |
| Function | ||
| Function | Counter  | |
| Function [2] | frequency | |
| Function [3] | direction of rotation | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection [3] | active binary signal 24 V DC | |
| Connection | channel I: 1+, 2- direction: 4+, 5- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | in frequency + counter mode: 12.5 ms otherwise 20 µs | |
| Operating frequency | 0 ... 15 kHz in frequency + counter mode ... 40 Hz | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Status LED (1) red: line fault | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 90 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PTB 03 ATEX 2042 | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ic] IIC T4 Gc | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| General specifications | ||
|---|---|---|
| Suitable components | backplane LB9024S , LB8105* , LB8106* , LB8108* , LB8109* , LB8107* | |
| Slots | ||
| Bus coupler | 2 | |
| Supply | 3 | |
| Output shut-down | 5 SIL2 output shutdown segments slots 3 ... 5, 6 ... 10, 11 ... 15, 16 ... 20, 21 ... 24 | |
| I/O modules (single width) | max. 22 | |
| I/O modules (dual width) | max. 11 | |
| Supply | ||
| Maximum safe voltage | 60 V DC (SELV/PELV) | |
| Input voltage range | 18 ... 32 V DC (SELV/PELV) | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS DP/DP-V1 or MODBUS RTU , depends on bus coupler | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 2170 g | |
| Dimensions | (W x H x D) 605 x 127 x 80 mm (23.8 x 5 x 3.15 inch) , without modules | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Описание оборудования | ||
|---|---|---|
| Field Unit, Polyester (GRP) | ||
| General specifications | ||
|---|---|---|
| Installed components | backplane LB9023A | |
| Slots | ||
| Bus coupler | 1 | |
| Supply | 1 | |
| I/O modules (single width) | max. 8 | |
| I/O modules (dual width) | max. 4 | |
| Supply | ||
| Connection | screw terminals, max. 10 mm2 | |
| Rated voltage | 24 V DC | |
| Maximum safe voltage | 60 V | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS DP/DP-V1 or MODBUS RTU , depends on bus coupler | |
| Electrical specifications | ||
| Permissible power | wall mounting: 43 W (at 40 °C (104 °F)) , 21.5 W (at 50 °C (122 °F)) | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 55 °C (-4 ... 131 °F) at T4 , depending on the permissible power | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP66, NEMA 4X | |
| Mass | approx. 10 kg , without modules | |
| Dimensions | (W x H x D) 350 x 306 x 215 mm (13.8 x 12 x 8.5 inch) | |
| Mounting | thru-holes Ø11 mm | |
| Data for application in connection with hazardous areas | ||
| Statement of conformity | PF 08 CERT 1267 | |
| Group, category, type of protection | II 3 G Ex nA nC [ic] IIC/IIB T4 II 3 (2) G Ex nA nC [ib] IIC T4 II 3 (1) G Ex nA nC [ia] IIC/IIB T4 II 3 D Ex tD A22 IP65 T 130°C II (2) D [Ex ib] IIIC II (1) D [Ex ia] IIIC | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2005 EN 61241-0:2006 EN 61241-1:2004 EN 61241-11:2006 EN 61010-1:2001 | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power dissipation | 2 W | |
| Power consumption | 3 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Analog input | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | pressure converter | |
| Field device [2] | flow converter | |
| Field device [3] | level converter | |
| Field device [4] | Temperature Converter | |
| Field device interface | ||
| Connection | 2-wire transmitter | |
| Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
| Transmitter supply voltage | min. 15 V at 20 mA 21.5 V at 4 mA | |
| Input resistance | 15 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
| Short-circuit | factory setting: > 21 mA Can be parameterized in the range 0 ... 22 mA | |
| Open-circuit | factory setting: < 3.6 mA Can be parameterized in the range 0 ... 22 mA | |
| HART communication | yes | |
| HART secondary variable | yes | |
| Analog output | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | Proportional Valve | |
| Field device [2] | I/P converters | |
| Field device [3] | on-site display | |
| Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
| Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
| Short-circuit | factory setting: < 50 &Omega configurable between 0 ... 26 mA | |
| Open-circuit | deviation of preset output value > 0.5 mA | |
| Load | 750 &Omega max. | |
| HART communication | yes | |
| HART secondary variable | yes | |
| Watchdog | output off 0.5 s after serious fault | |
| Digital input | ||
| Number of channels | 4 | |
| Sensor interface | ||
| Connection [2] | volt-free contact | |
| Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
| Digital signals (active) | ||
| Switching point: ON | > 2.1 mA | |
| Switching point: OFF | < 1.2 mA | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) | |
| Short-circuit | > 7 mA | |
| Open-circuit | < 0.1 mA | |
| Digital output | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | terminals 1+, 2-, 3+, 4-, 5+, 6-, 7+, 8- | |
| Drive capability | 12 V / 22 mA | |
| Open loop voltage | min. 22.7 V | |
| Current limit | 22 mA | |
| Internal resistor | 385 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Test current | 0.4 mA | |
| Short-circuit | < 50 &Omega | |
| Open-circuit | < 0.2 mA | |
| Transfer characteristics | ||
| Deviation | ||
| After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
| Refresh time | approx. 100 ms (4 channels) | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) Configuration LED (AI, AO, DI, DO) white: selected channel mode | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2000 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 100 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Certificate | BVS 12 ATEX E 115 X | |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc | |
| Galvanic isolation | ||
| Rated voltage | 250 V field circuits to control and supply circuits | |
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | BVS 12 ATEX E 115 X | |
| IECEx approval | BVS 11.0068X | |
| Approved for | Ex nAc [ic] IIC T4 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| Bureau Veritas Marine | 22449/B0 BV | |