| Описание оборудования | ||
|---|---|---|
| Measuring sensor with multiple switch points, small design, background suppression and more adjustable operating modes, IO-Link interface | ||
| Описание оборудования | ||
|---|---|---|
| Switch Amplifier | ||
| Mechanical specifications | ||
|---|---|---|
| Thread type | metric ISO pitch 1.5 mm | |
| Thread size | M20 (TD) | |
| Thread type female | metric ISO pitch 1.5 mm | |
| Thread size female | M16 (TF) | |
| Degree of protection | IP66 / IP68 | |
| Material | ||
| Washer gasket | aramid fibers bonded with NBR | |
| Adapter | brass, nickel-plated | |
| O-Ring | chloroprene | |
| Mass | 39 g | |
| Dimensions | ||
| Width across corners | 27.5 mm (D2) | |
| Length outside enclosure | 4 mm (H) | |
| Width across flats | 25 mm (SW1) | |
| Thread length | 15 mm (TL) | |
| Thread length female | 19 mm (TLF) | |
| Total length | 19 mm (L) | |
| Tightening torque | ||
| Nut torque at enclosure | 6 Nm (SW1) | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 100 °C (-40 ... 212 °F) washer gasket -40 ... 80 °C (-40 ... 176 °F) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CESI 15ATEX029X | |
| Marking | II 2 GD Ex d IIC Gb Ex e IIC Gb Ex tb IIIC Db | |
| International approvals | ||
| IECEx approval | IECEx CES 15.0006X | |
| EAC approval | TC RU C-TR.GB05.B.00918 | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Scope of delivery | Adapter Lock nut washer gasket brief instructions | |
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Описание оборудования | ||
|---|---|---|
| Female receptacle, M12/ 1/2" NPT, 4-pin | ||
| Описание оборудования | ||
|---|---|---|
| Universal sensor system for detecting vehicles | ||
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 23+, 24- | |
| Rated voltage | 20 ... 30 V DC | |
| Rated current | approx. 130 mA | |
| Power dissipation | 2 W | |
| Power consumption | 2.5 W | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3 | |
| Input I | ||
| Input signal | 0/4 ... 20 mA | |
| Available voltage | &ge 15 V at 20 mA | |
| Open circuit voltage/short-circuit current | 24 V / 33 mA | |
| Input resistance | 45 &Omega (terminals 2, 3) | |
| Line fault detection | breakage I < 0.2 mA short-circuit I > 22 mA | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 Output: analog terminals 8+, 7- | |
| Output signal | 0 ... 20 mA or 4 ... 20 mA | |
| Output I, II | signal, relay | |
| Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 V DC / 2 A | |
| Mechanical life | 5 x 107 switching cycles | |
| Output III | Signal, analog | |
| Current range | 0 ... 20 mA or 4 ... 20 mA | |
| Open loop voltage | max. 24 V DC | |
| Load | max. 650 &Omega | |
| Fault signal | downscale I &le 3.6 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) | |
| Indicators/settings | ||
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons via PACTware | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| International approvals | ||
| UL approval | E223772 | |
| HART signal channels (non-intrinsically safe) | ||
|---|---|---|
| Load resistor | 220 &Omega , switchable on | |
| Interface | ||
| Type | multiplexer connection : 26-pin NFP-26A (Yamaichi) | |
| Signal lines | ||
| Rated current | max. 30 mA per channel | |
| Indicators/settings | ||
| DIP switch | selection of operating mode: - ON: without load resistor - OFF: with load resistor | |
| Factory setting | DIP switches S1 and S2: ON | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 50 °C (32 ... 122 °F) | |
| Storage temperature | -15 ... 50 °C (5 ... 122 °F) | |
| Relative humidity | &le 93 % non-condensing | |
| Shock resistance | 15 g , 11 ms | |
| Vibration resistance | 1 g , 10 ... 150 Hz | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | ||
| Field side | screw terminals , green | |
| Control side | screw terminals , green HART : 1 x IDC plug, 26-pin | |
| Core cross-section | screw terminals: 0.25 ... 1.5 mm2 (24 ... 16 AWG) | |
| Mass | approx. 200 g | |
| Dimensions | 110 x 125 x 67 mm (4.3 x 4.9 x 2.6 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 55 °C (-4 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: fixed screw terminals control side: fixed screw terminals RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 222 x 122 x 79 mm (8.7 x 4.8 x 3.1 inch) with HiDMux2700: 222 x 122 x 208 mm (8.7 x 4.8 x 8.2 inch) | |
| Mounting | DIN rail mounting | |
| Описание оборудования | ||
|---|---|---|
| 24 V DC | ||
| Описание оборудования | ||
|---|---|---|
| Transmission range 4 mA ... 20 mA | ||
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 9+, 10- | |
| Rated voltage | 19 ... 30 V DC | |
| Ripple | within the supply tolerance | |
| Rated current | < 20 mA | |
| Power consumption | 0.35 W (24 V and 1 mA sense current) | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3, 4 | |
| Line fault detection | yes , at Pt100 | |
| Lead resistance | &le 10 % of resistance value | |
| Transmission range | 0 ... 10 mA | |
| Available voltage | 9 V | |
| Line fault detection | 8 nA | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 5-, 7-, 6+, 8+ | |
| Current | 0 ... 10 mA | |
| Available voltage | 0 ... 4.2 V | |
| Fault signal | < 10 &Omega or > 400 &Omega, depending on lead disconnected (measuring current &le 1 mA) > 400 &Omega, terminal 3 lead disconnected in 2-/4-wire (measuring current &le 0.3 mA) | |
| Transfer characteristics | ||
| Accuracy | 0.1 % | |
| Deviation | 4-wire Im &ge 1 mA: ±0.1 % of Rm or ± 0.1 &Omega (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: ± 1 % of Rm or 1 &Omega (the larger value is applicable). 3-wire Im &ge 1 mA: (±0.1 % - 0.1 &Omega Offset) or ± 0.2 &Omega (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: (±1 % - 0.1 &Omega Offset) or ± 1.1 &Omega (the larger value is applicable) | |
| Rise time | signal response time &le 2 ms (10 ... 90 %) response to application of Im: Rm > 50 &Omega and Im < 5mA: < 5ms response to application of Im: Rm > 30 &Omega and Im < 5mA: < 10ms response to application of Im: Rm > 18 &Omega and Im < 5mA: < 20ms | |
| Indicators/settings | ||
| Display elements | LED | |
| Control elements | DIP-switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 100 g | |
| Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BASEEFA 10 ATEX 0061 | |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Certificate | BASEEFA 10 ATEX 0062X | |
| Marking | II 3G Ex nA II T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0129 (cFMus) | |
| UL approval | ||
| Control drawing | 116-0332 (cULus) | |
| IECEx approval | IECEx BAS 10.0024 IECEx BAS 10.0025X | |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
| Accessories | ||
| Designation | optional accessories: insertion bridge EBP 2- 5 | |
| Описание оборудования | ||
|---|---|---|
| Field Unit, Polyester (GRP) | ||
| General specifications | ||
|---|---|---|
| Installed components | backplane LB9023A | |
| Slots | ||
| Bus coupler | 1 | |
| Supply | 1 | |
| I/O modules (single width) | max. 8 | |
| I/O modules (dual width) | max. 4 | |
| Supply | ||
| Connection | screw terminals, max. 10 mm2 | |
| Rated voltage | 24 V DC | |
| Maximum safe voltage | 60 V | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS DP/DP-V1 or MODBUS RTU , depends on bus coupler | |
| Electrical specifications | ||
| Permissible power | wall mounting: 43 W (at 40 °C (104 °F)) , 21.5 W (at 50 °C (122 °F)) | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 55 °C (-4 ... 131 °F) at T4 , depending on the permissible power | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP66, NEMA 4X | |
| Mass | approx. 10 kg , without modules | |
| Dimensions | (W x H x D) 350 x 306 x 215 mm (13.8 x 12 x 8.5 inch) | |
| Mounting | thru-holes Ø11 mm | |
| Data for application in connection with hazardous areas | ||
| Statement of conformity | PF 08 CERT 1267 | |
| Group, category, type of protection | II 3 G Ex nA nC [ic] IIC/IIB T4 II 3 (2) G Ex nA nC [ib] IIC T4 II 3 (1) G Ex nA nC [ia] IIC/IIB T4 II 3 D Ex tD A22 IP65 T 130°C II (2) D [Ex ib] IIIC II (1) D [Ex ia] IIIC | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2005 EN 61241-0:2006 EN 61241-1:2004 EN 61241-11:2006 EN 61010-1:2001 | |
| Описание оборудования | ||
|---|---|---|
| Female connector, M12, 4-pin, screened, field attachable | ||
| Supply | ||
|---|---|---|
| Rated voltage | 8.2 V ± 2 V | |
| Current consumption | < 1.0 mA unswitched (de-energized at the bottom), > 2.2 mA switched (floated up at the top) | |
| Reverse polarity protection | yes | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 60947-5-2:2007+A1:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Application | ||
| Description | Proximity switch with operation ball | |
| Function and system design | ||
| Equipment architecture | A measuring system consists of a float switch LFL1-**-N and a transformer isolated barrier, e. g. KFD2-SR2-Ex1.W. | |
| Operating conditions | ||
| Installation conditions | ||
| Installation instructions | range of application and minimum length between mounting and float: - PVC version: &ge 50 mm (2 inch), preferred for water - PUR version: &ge 100 mm (4 inch), preferred for fuels, heating oils, oily fluids - CSM/CM version: &ge 100 mm (4 inch), preferred for many acids and lyes mounting: - The float switch is mounted either from sidewards through a cable gland &ge G1A into the vessel or - by means of a counter weight or rods (e. g. float switch combination) from the top. The pivot of the cable should always be horizontal. | |
| Process conditions | ||
| Process pressure (static pressure) | sleeve design: &le 3 bar at 20 °C (68 °F) ball design: &le 2 bar at 20 °C (68 °F) | |
| Density | sleeve design: &ge 0.8 g/cm3 ball design: &ge 0.6 g/cm3 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Altitude | &le 2000 m above MSL | |
| Mechanical specifications | ||
| Degree of protection | IP68 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | TÜV 99 ATEX 1407 | |
| Group, category, type of protection | II 2G Ex ia IIB T5 | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 | |
| Mechanical construction | ||
| Material | float: PP (Polypropylene) cable: - PVC version: PVC cable, highly flexible (2 x 0.75 mm2) - PUR version: PUR cable, highly flexible (2 x 0.50 mm2) - CSM/CM version: CSM/CM cable (chlorinated polyethylene, (2 x 0.75 mm2)) | |
| Описание оборудования | ||
|---|---|---|
| Handheld (125 kHz) for System IDENTControl | ||
| Описание оборудования | ||
|---|---|---|
| Charger for OHV200 with built-in Bluetooth modem | ||
| Conformity | ||
|---|---|---|
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 50 °C (-4 ... 122 °F) | |
| Storage temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP66 | |
| Connection | 1 cable gland M16 x 1.5 for cable diameter 5,5 ... 10 mm, blue color 1 M12 x 5 connector for connecting a barcode reader type PSCAN-D 1 PE bolt M6 | |
| Material | Housing: antistatic glass reinforced polyester, black color Holder for barcode reader: stainless steel 1.4301 (304) M12 cable gland: stainless steel 1.4301 (304) PE bolt: brass | |
| Mass | approx. 2000 g | |
| Dimensions | 155 x 145 x 217 mm | |
| Data for application in connection with hazardous areas | ||
| Statement of conformity | ||
| Group, category, type of protection, temperature class | simple apparatus for use in gas/dust atmosphere according to EN 60079-11, temperature class T4 | |
| Voltage | 30 V | |
| Current | 500 mA | |
| Power | 2 W | |
| General information | ||
| Supplementary information | Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Описание оборудования | ||
|---|---|---|
| Switch Amplifier | ||
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power Rail or terminals 23+, 24- | |
| Rated voltage | 19 ... 30 V DC | |
| Rated current | approx. 120 mA at 24 V DC | |
| Power dissipation | 2.3 W | |
| Power consumption | 2.9 W | |
| HART signal channels (intrinsically safe) | ||
| Conformity | HART field device input (revision 5 to 7) | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3, 4, 5, 6 | |
| Open circuit voltage/short-circuit current | typ. 24 V / 28 mA | |
| Input resistance | 250 &Omega , 5 % (terminals 2, 3 and with jumper on 5, 6) | |
| Available voltage | &ge 15.5 V at 20 mA, short-circuit protected | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 7, 8, 9 , output II: terminals 13, 14, 15 , output III: terminals 19, 20, 21 | |
| Output signal | analog | |
| Current range | 4 ... 20 mA , (source or sink mode) | |
| Load | max. 650 &Omega , source mode | |
| Voltage range | 5 ... 30 V , sink mode from external supply | |
| Fault signal | downscale I &le 2 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) or hold measurement value | |
| Other outputs | HART communicator on terminals 22, 24 | |
| Collective error message | Power Rail and LED red | |
| Indicators/settings | ||
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons via PACTware | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BASEEFA 07 ATEX 0174 | |
| Marking | II (1)GD [Ex ia] IIC, [Ex iaD] | |
| Certificate | PF 07 CERT 1142 X | |
| Marking | II 3G Ex nA II T4 X | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0129 | |
| IECEx approval | ||
| IECEx certificate | IECEx BAS 07.0047 | |
| IECEx marking | [Ex ia] IIC , [Ex iaD] | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 11+, 12- | |
| Rated voltage | 20 ... 35 V DC | |
| Ripple | within the supply tolerance | |
| Power dissipation | 0.5 W | |
| Power consumption | 0.6 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 4-, 5-, 3+, 2+, 1+ | |
| Potentiometer | ||
| Types of measuring | 3-, 4-, 5-wire technology | |
| Lead resistance | 5 % of the potentiometer resistance (adjustable) | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 7-, 8+ | |
| Voltage output | 0 ... 10 V | |
| Output resistance | max. 30 &Omega | |
| Transfer characteristics | ||
| Accuracy | 0.05 % | |
| Rise time | 10 to 90 % &le 8 ms 10 to 90 % within 1 % of span &le 25 ms | |
| Indicators/settings | ||
| Control elements | potentiometer | |
| Configuration | via potentiometer | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 120 g | |
| Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 00 ATEX 7171 | |
| Marking | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) | |
| Certificate | TÜV 02 ATEX 1797 X | |
| Marking | II 3G Ex nA II T4 | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0129 | |
| UL approval | ||
| Control drawing | 116-0173 (cULus) | |
| CSA approval | ||
| Control drawing | 116-0132 | |
| IECEx approval | IECEx BAS 10.0060 IECEx BAS 10.0061X | |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA II T4 Gc | |
| Описание оборудования | ||
|---|---|---|
| Current output 0/4 mA ... 20 mA | ||
| Описание оборудования | ||
|---|---|---|
| Current output 0/4 mA ... 20 mA | ||
| Supply | ||
|---|---|---|
| Rated voltage | 3.6 V DC , battery operated | |
| Power dissipation/power consumption | < 0.09 W | |
| Input | ||
| Connection | terminals 1, 2, 3, 4 | |
| RTD | type Pt100, Pt1000 (IEC 751: 1995 GOST: alpha = 0.391) | |
| Connection | 2-wire: 2 sensors, 3- or 4-wire: 1 sensor | |
| Lead resistance | max. 10 &Omega | |
| Measuring circuit monitoring | sensor breakage | |
| Thermocouples | type E, J, K, T (IEC 584-1) | |
| Cold junction compensation | internal , external | |
| Measuring circuit monitoring | sensor breakage | |
| Measurement range | type K: -270 ... 1370 °C type T: -270 ... 400 °C type E: -270 ... 1000 °C type J: -210 ... 1200 °C | |
| Resistor | ||
| Measurement range | 0 ... 500 &Omega , 0 ... 4000 &Omega | |
| Voltage | mV Input | |
| Measurement range | -100 ... 100 mV , 0 ... 300 mV | |
| Input resistance | &ge 1 M&Omega | |
| Output | ||
| Output variables | PV: input 1 (°C, &Omega, mV) SV: input 2 (°C, &Omega, mV) TV: CJC temperature (°C) estimated battery life (days) battery voltage (volts) residual battery capacity (%) | |
| Transfer characteristics | ||
| Accuracy | - internal cold junction compensation error ± 1,5 °C (typ. acc. to IEC 61298-3) - external cold junction compensation error ± 1 °C (typ.) - resolution error < 0.1 °C - accuracy TC ± 20 µV - accuracy RTD: ± 100 m&Omega | |
| Indicators/settings | ||
| Parameter assignment | - sampling period: 1, 2, 5, 10, 30 seconds or 1, 2, 5, 10, 30, 60 minutes - transmit power: configurable 0 dBm or 10 dBm (EIRP) - sensor type - mapping of input measuring values 1 and 2 into primary variable (PV) and secondary variable (SV) - publishing of up to three messages from the device, transmission rate selectable from 4 seconds to 60 minutes | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2004/108/EC | EN 61326-1:2006 | |
| Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
| Directive 99/5/EC | ETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001 | |
| FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Accuracy | IEC 61298-3 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -20 ... 70 °C (-4 ... 158 °F) | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
| Mechanical specifications | ||
| Degree of protection | IP65 | |
| Mass | approx. 1000 g | |
| Dimensions | 77 x 129 x 177 mm (3 x 5.08 x 6.97 inch) | |
| Mounting | panel or pole mounting | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | IMQ 09 ATEX 008X | |
| Group, category, type of protection | II 2(1)G Ex ia [ia] IIC T4 | |
| Directive conformity | ||
| Directive 94/9/EC | EN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007 | |
| International approvals | ||
| FM approval | CoC 3042534 | |
| IECEx approval | IECEx INE 09.0025X | |
| Approved for | Ex ia IIC T4 | |
| Accessories | ||
| Designation | battery W-BAT-B1-Li mandatory for use in connection with hazardous areas (order separately) Mounting set W-ACC-F7MK External cold junction compensation W-ACC-CJC | |
| Описание оборудования | ||
|---|---|---|
| Sensor output interface terminal with lead breakage monitoring | ||
| Описание оборудования | ||
|---|---|---|
| Industrial Box Thin Client | ||
| Описание оборудования | ||
|---|---|---|
| Valve connector Form A, non pre-wired | ||
| General specifications | ||
|---|---|---|
| Signal type | Digital Output | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 3 | |
| Performance level (PL) | PL e | |
| Supply | ||
| Rated voltage | loop powered | |
| Power dissipation | < 1.3 W | |
| Power consumption | < 1.3 W | |
| Input | ||
| Connection side | control side | |
| Connection | Input terminals 5, 6 test input terminals 7, 8, 9, 10 | |
| Pulse/Pause ratio | 150 ms / 150 ms | |
| Signal level | 0-signal: -5 ... 5 V 1-signal: 19 ... 26.5 V | |
| Rated current | 0-signal: typ. 1.6 mA at 1.5 V typ. 8 mA at 3 V (maximum leakage current DO card) 1-signal: &ge 36 mA (minmum load current DO card) | |
| Output | ||
| Connection | terminals 1, 2 | |
| Contact loading | 253 V AC/3 A/cos &phi 0.7 30 V DC/3 A resistive load | |
| Minimum switch current | 10 mA / 24 V DC | |
| Energized/De-energized delay | 150 ms / 150 ms | |
| Mechanical life | 5 x 106 switching cycles | |
| Transfer characteristics | ||
| Switching frequency | < 3 Hz | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Machinery Directive | ||
| Directive 2006/42/EC | EN 62061:2005+AC:2010+A1:2013+A2:2015 , EN/ISO 13849-1:2015 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 | |
| Degree of protection | IEC 60529:2013 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating. | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 100 g | |
| Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 15 CERT 3932 X | |
| Marking | II 3G Ex nC ec IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-15:2010 | |
| General specifications | ||
|---|---|---|
| Signal type | Digital Output | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 3 | |
| Supply | ||
| Rated voltage | loop powered | |
| Power dissipation | 0.8 W | |
| Input | ||
| Connection side | control side | |
| Connection | terminals 7, 8, 9 | |
| Input current | &le 21 mA per channel | |
| Output | ||
| Safety note | Attention! Combination of output Ex i with output not Ex i is not permitted. If load voltage > 50 V, de-energize before removing the terminals. | |
| Connection side | field side | |
| Connection | terminals 1, 2, 3 4, 5, 6 | |
| Contact loading | 230 V AC/2 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
| Energized/De-energized delay | approx. 10 ms / approx. 5 ms | |
| Mechanical life | 5 x 106 switching cycles | |
| Transfer characteristics | ||
| Switching frequency | < 10 Hz | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 65 °C (-4 ... 149 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 100 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | DMT 00 ATEX E 016 | |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Certificate | TÜV 00 ATEX 1621 X | |
| Marking | II 3G Ex nA nC IIC T4 | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0261 | |
| CSA approval | ||
| Control drawing | 116-0156 | |
| IECEx approval | IECEx BVS 10.0025 | |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
| Описание оборудования | ||
|---|---|---|
| Retroreflective sensor for glass detection, M18 threaded housing design, plastic housing, front optical face, 2.5 m detection range, red light, light/dark on, DC version, 2 PNP outputs, M12 plug | ||