| Описание оборудования | ||
|---|---|---|
| 24 V DC | ||
| Описание оборудования | ||
|---|---|---|
| 24 V DC | ||
| General specifications | ||
|---|---|---|
| Signal type | Digital Input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | terminals 14, 15 | |
| Rated voltage | 207 ... 253 V AC, 45 ... 65 Hz | |
| Power dissipation | 1.2 W | |
| Power consumption | max. 1.3 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1+, 2+, 3- 4+, 5+, 6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
| Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
| Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 7, 8, 9 output II: terminals 10, 11, 12 | |
| Output I, II | signal relay | |
| Contact loading | 253 V AC/2 A/cos &phi > 0.7 126.5 V AC/4 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
| Mechanical life | 107 switching cycles | |
| Transfer characteristics | ||
| Switching frequency | &le 10 Hz | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 150 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 00 ATEX 2081 | |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0035 | |
| UL approval | ||
| Control drawing | 116-0145 | |
| CSA approval | ||
| Control drawing | 116-0047 | |
| IECEx approval | IECEx PTB 11.0031 | |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
| General specifications | ||
|---|---|---|
| Signal type | Digital Input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 14+, 15- | |
| Rated voltage | 20 ... 30 V DC | |
| Ripple | &le 10 % | |
| Rated current | &le 50 mA | |
| Power dissipation | 1 W | |
| Power consumption | < 1.3 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1+, 2+, 3- 4+, 5+, 6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
| Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
| Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 7, 8, 9 output II: terminals 10, 11, 12 | |
| Output I, II | signal, relay | |
| Contact loading | 253 V AC/2 A/cos &phi > 0.7 126.5 V AC/4 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
| Minimum switch current | 2 mA / 24 V DC | |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
| Mechanical life | 107 switching cycles | |
| Transfer characteristics | ||
| Switching frequency | &le 10 Hz | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Control elements | DIP-switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 150 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 00 ATEX 2080 | |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Fault indication output | ||
| Maximum safe voltage | 40 V DC (Attention! Um is no rated voltage.) | |
| Certificate | PF 08 CERT 0803 | |
| Marking | II (3)G [Ex ic Gc] IIC | |
| Certificate | TÜV 99 ATEX 1493 X | |
| Marking | II 3G Ex nA nC IIC T4 | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0035 | |
| CSA approval | ||
| Control drawing | 116-0047 | |
| IECEx approval | IECEx PTB 11.0034 | |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
| General specifications | ||
|---|---|---|
| Signal type | Digital Input | |
| Supply | ||
| Connection | Power Rail or terminals 14+, 15- | |
| Rated voltage | 19 ... 30 V DC | |
| Ripple | &le 10 % | |
| Rated current | 45 ... 70 mA | |
| Power dissipation | 1.2 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1-, 2+, 3- 4-, 5+, 6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
| Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
| Pulse/Pause ratio | min. 35 ms / min. 35 ms (non-AC operation) min. 70 ms / min. 70 ms (AC operation) | |
| Line fault detection | breakage I &le 0.15 mA , short-circuit I > 6 mA | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 7, 8 output II: terminals 8, 9 output III: terminals 10, 11 output IV: terminals 11, 12 | |
| Output I ... IV | Signal I ... Signal IV relay | |
| Contact loading | 253 V AC/2 A /cos &phi > 0.7 40 V DC/2 A resistive load | |
| Energized/De-energized delay | approx. 30 ms / approx. 30 ms | |
| Mechanical life | 5 x 106 switching cycles | |
| Collective error message | Power Rail | |
| Transfer characteristics | ||
| Switching frequency | &le 10 Hz (non-AC operation) &le 3 Hz (AC operation) | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Control elements | DIP-switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 150 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | ZELM 99 ATEX 0009 | |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Fault indication output | ||
| Maximum safe voltage | 40 V DC | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
| International approvals | ||
| UL approval | ||
| Control drawing | 116-0145 | |
| IECEx approval | IECEx TUN 04.0003 | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I | |
| Описание оборудования | ||
|---|---|---|
| 230 V AC | ||
| Описание оборудования | ||
|---|---|---|
| current limit 45 mA | ||
| Описание оборудования | ||
|---|---|---|
| Input 4 mA ... 20 mA Output 4 mA ... 20 mA | ||
| Описание оборудования | ||
|---|---|---|
| Input 0/4 mA ... 20 mA 2 x Output 0/4 mA ... 20 mA | ||
| Описание оборудования | ||
|---|---|---|
| Input 0/4 mA ... 20 mA Output 0/4 mA ... 20 mA | ||
| Описание оборудования | ||
|---|---|---|
| Input 0/4 mA ... 20 mA Output 0/4 mA ... 20 mA (current sink) | ||
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 23+, 24- | |
| Rated voltage | 20 ... 30 V DC | |
| Rated current | approx. 130 mA | |
| Power dissipation | 2 W | |
| Power consumption | 2.5 W | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3 | |
| Input I | ||
| Input signal | 0/4 ... 20 mA | |
| Available voltage | &ge 15 V at 20 mA | |
| Open circuit voltage/short-circuit current | 24 V / 33 mA | |
| Input resistance | 45 &Omega (terminals 2, 3) | |
| Line fault detection | breakage I < 0.2 mA short-circuit I > 22 mA | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- | |
| Output signal | 0 ... 20 mA or 4 ... 20 mA | |
| Output I, II | signal, relay | |
| Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 DC / 2 A | |
| Mechanical life | 5 x 107 switching cycles | |
| Output III | Signal, analog | |
| Current range | 0 ... 20 mA or 4 ... 20 mA | |
| Open loop voltage | max. 24 V DC | |
| Load | max. 650 &Omega | |
| Fault signal | downscale I &le 3.6 mA, upscale I &ge 21 mA (acc. NAMUR NE43) | |
| Indicators/settings | ||
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons via PACTware | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | TÜV 01 ATEX 1701 | |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Certificate | TÜV 02 ATEX 1885 X | |
| Marking | II 3G Ex nA nC IIC T4 | |
| Output I, II | ||
| Contact loading | 50 V AC/2 A/cos &phi > 0.7 40 V DC/1 A resistive load | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 16-554FM-12 (cFMus) | |
| UL approval | E223772 | |
| IECEx approval | IECEx TUN 09.0007 | |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
| General specifications | ||
|---|---|---|
| Signal type | Analog output | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 9+, 10- | |
| Rated voltage | 19 ... 30 V DC | |
| Ripple | &le 10 % | |
| Rated current | &le 30 mA | |
| Power dissipation | &le 600 mW | |
| Power consumption | &le 700 mW | |
| Input | ||
| Connection side | control side | |
| Connection | terminals 5-, 6+ | |
| Input signal | 4 ... 20 mA limited to approx. 30 mA | |
| Voltage drop | depending on switch configuration open loop voltage of the control system < 23 V: approx. 6 V at 20 mA open loop voltage of the control system < 27 V: approx. 10 V at 20 mA | |
| Input resistance | > 100 k&Omega, with field wiring open | |
| Output | ||
| Connection side | field side | |
| Connection | terminals 1+, 2- | |
| Current | 4 ... 20 mA | |
| Load | 0 ... 650 &Omega | |
| Voltage | &ge 13 V at 20 mA | |
| Ripple | 20 mV rms | |
| Transfer characteristics | ||
| Accuracy | 0.1 % | |
| Deviation | at 20 °C (68 °F), 0/4 ... 20 mA &le ± 0.1 % incl. non-linearity and hysteresis | |
| Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) | |
| Rise time | 10 to 90 % &le 100 ms | |
| Indicators/settings | ||
| Display elements | LED | |
| Control elements | DIP-switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 100 g | |
| Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CESI 06 ATEX 021 | |
| Marking | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I | |
| Certificate | PF 06 CERT 0973 X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0419 (cFMus) | |
| UL approval | ||
| Control drawing | 116-0420 (cULus) | |
| IECEx approval | IECEx CES 06.0001 | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I | |
| Описание оборудования | ||
|---|---|---|
| 24 V DC | ||
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 9+, 10- | |
| Rated voltage | 19 ... 30 V DC | |
| Ripple | within the supply tolerance | |
| Rated current | < 20 mA | |
| Power consumption | 0.35 W (24 V and 1 mA sense current) | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3, 4 | |
| Line fault detection | yes , at Pt100 | |
| Lead resistance | &le 10 % of resistance value | |
| Transmission range | 0 ... 10 mA | |
| Available voltage | 9 V | |
| Line fault detection | 8 nA | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 5-, 7-, 6+, 8+ | |
| Current | 0 ... 10 mA | |
| Available voltage | 0 ... 4.2 V | |
| Fault signal | < 10 &Omega or > 400 &Omega, depending on lead disconnected (measuring current &le 1 mA) > 400 &Omega, terminal 3 lead disconnected in 2-/4-wire (measuring current &le 0.3 mA) | |
| Transfer characteristics | ||
| Accuracy | 0.1 % | |
| Deviation | 4-wire Im &ge 1 mA: ±0.1 % of Rm or ± 0.1 &Omega (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: ± 1 % of Rm or 1 &Omega (the larger value is applicable). 3-wire Im &ge 1 mA: (±0.1 % - 0.1 &Omega Offset) or ± 0.2 &Omega (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: (±1 % - 0.1 &Omega Offset) or ± 1.1 &Omega (the larger value is applicable) | |
| Rise time | signal response time &le 2 ms (10 ... 90 %) response to application of Im: Rm > 50 &Omega and Im < 5mA: < 5ms response to application of Im: Rm > 30 &Omega and Im < 5mA: < 10ms response to application of Im: Rm > 18 &Omega and Im < 5mA: < 20ms | |
| Indicators/settings | ||
| Display elements | LED | |
| Control elements | DIP-switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 100 g | |
| Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BASEEFA 10 ATEX 0061 | |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Certificate | BASEEFA 10 ATEX 0062X | |
| Marking | II 3G Ex nA II T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0129 (cFMus) | |
| UL approval | ||
| Control drawing | 116-0332 (cULus) | |
| IECEx approval | IECEx BAS 10.0024 IECEx BAS 10.0025X | |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
| Accessories | ||
| Designation | optional accessories: insertion bridge EBP 2- 5 | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 11+, 12- | |
| Rated voltage | 20 ... 35 V DC | |
| Ripple | within the supply tolerance | |
| Power dissipation | 0.5 W | |
| Power consumption | 0.6 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 4-, 5-, 3+, 2+, 1+ | |
| Potentiometer | ||
| Types of measuring | 3-, 4-, 5-wire technology | |
| Lead resistance | 5 % of the potentiometer resistance (adjustable) | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 7-, 8+ | |
| Voltage output | 0 ... 10 V | |
| Output resistance | max. 30 &Omega | |
| Transfer characteristics | ||
| Accuracy | 0.05 % | |
| Rise time | 10 to 90 % &le 8 ms 10 to 90 % within 1 % of span &le 25 ms | |
| Indicators/settings | ||
| Control elements | potentiometer | |
| Configuration | via potentiometer | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 120 g | |
| Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 00 ATEX 7171 | |
| Marking | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) | |
| Certificate | TÜV 02 ATEX 1797 X | |
| Marking | II 3G Ex nA II T4 | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0129 | |
| UL approval | ||
| Control drawing | 116-0173 (cULus) | |
| CSA approval | ||
| Control drawing | 116-0132 | |
| IECEx approval | IECEx BAS 10.0060 IECEx BAS 10.0061X | |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA II T4 Gc | |
| Описание оборудования | ||
|---|---|---|
| Current output 0/4 mA ... 20 mA | ||
| General specifications | ||
|---|---|---|
| Signal type | Digital Output | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 3 | |
| Supply | ||
| Rated voltage | loop powered | |
| Power dissipation | 0.8 W | |
| Input | ||
| Connection side | control side | |
| Connection | terminals 7, 8, 9 | |
| Input current | &le 21 mA per channel | |
| Output | ||
| Safety note | Attention! Combination of output Ex i with output not Ex i is not permitted. If load voltage > 50 V, de-energize before removing the terminals. | |
| Connection side | field side | |
| Connection | terminals 1, 2, 3 4, 5, 6 | |
| Contact loading | 230 V AC/2 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
| Energized/De-energized delay | approx. 10 ms / approx. 5 ms | |
| Mechanical life | 5 x 106 switching cycles | |
| Transfer characteristics | ||
| Switching frequency | < 10 Hz | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 65 °C (-4 ... 149 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 100 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | DMT 00 ATEX E 016 | |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Certificate | TÜV 00 ATEX 1621 X | |
| Marking | II 3G Ex nA nC IIC T4 | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0261 | |
| CSA approval | ||
| Control drawing | 116-0156 | |
| IECEx approval | IECEx BVS 10.0025 | |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
| Описание оборудования | ||
|---|---|---|
| 24 V DC | ||
| Описание оборудования | ||
|---|---|---|
| 230 V AC | ||
| Описание оборудования | ||
|---|---|---|
| 24 V DC | ||