| Supply |
|---|
| Rated voltage | 20 ... 30 V DC SELV/PELV |
| Power consumption | < 5 W |
| External bus |
|---|
| Connection | screw terminals for - 0.2 ... 4 mm2 (rigid wire) - 0.2 ... 2.5 mm2 (flexible wire) |
| Interface 1 | Ethernet 10 BASE-T/100 BASE-TX , full galvanic isolation |
| Protocol | HART UDP, MODBUS TCP |
| Interface 2 | RS-485 |
| Protocol | HART, MODBUS RTU |
| Transfer rate | max. 115 kBit/s |
| Galvanic isolation |
|---|
| Interface/interface | basic insulation according to IEC 61140, rated insulation voltage 50 Veff |
| Directive conformity |
|---|
| Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 |
| Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. |
| Directive 2014/53/EU | EN 300328: V2.1.1 EN 301489-17: V1.3.2 |
| FCC CFR47 Part 15 B and C | ANSI C63.4-2003 |
| Conformity |
|---|
| Degree of protection | IEC 60529 |
| Ambient conditions |
|---|
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 |
| Mechanical specifications |
|---|
| Degree of protection | IP66/IP67 |
| Mass | approx. 1 kg |
| Dimensions | 258 mm x 114 mm x 84 mm without antenna and cable glands |
| Mounting | panel mounting |
| Data for application in connection with hazardous areas |
|---|
| EU-Type Examination Certificate | FM 12 ATEX 0061 |
| Marking | II 3 G Ex nA IIC T4 Gc |
| Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
| International approvals |
|---|
| FM approval | Coc3042646 |
| Approved for | NI Class I, Div. 2, GPS A-D NI Class II, Class III, Div. 2, GPS E-G |
| IECEx approval | IECEx FMG 12.0002 |
| Approved for | Ex nA IIC T4 Gc , Ex nAc T4 |