Атол 30Ф не включается (заводской брак)
Валерий
14 января 2022
| Описание оборудования | ||
|---|---|---|
| Fieldbus Diagnostic Handheld | ||
| Supply | ||
|---|---|---|
| Rated voltage | 19.2 ... 35 V DC | |
| Rated current | 150 ... 100 mA | |
| Power dissipation | 3 W | |
| Ethernet Interface | ||
| Intrinsically safe port | 10 BASE-T/100 BASE-TX | |
| Non-intrinsically safe port | 10 BASE-T/100 BASE-TX | |
| Connection type | 2 x RJ-45 , IEC 60603-7 | |
| Connector pinout | socket TIA/EIA-568-B | |
| Transfer rate | 10/100 Mbit/s , Auto-Negotiation | |
| Operating mode | Half/Full Duplex | |
| Cable type | CAT5e S/FTP AWG 24, Installation cable, L/R ratio max. 10 µH/&Omega of all strand combinations | |
| I.S. cable length | typ. 100 m/20 °C | |
| Total cable length | typ. 200 m/20 °C | |
| Number of isolators | max. 2 in series connection | |
| Indicators/operating means | ||
| LED PWR | green: Power on | |
| LED ACT | yellow: communication active | |
| LED 10/100 | yellow ON: Transfer rate 100 MBit/s , OFF: 10 MBit/s | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Standard conformity | ||
| Galvanic isolation | EN 50020 | |
| Degree of protection | IEC 60529 | |
| Climatic conditions | DIN IEC 721 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ethernet | IEEE 802.3 , IEEE 802.3u | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | &le 95 % non-condensing | |
| Shock resistance | 15 g 11 ms | |
| Vibration resistance | 1 g 10 ... 150 Hz | |
| Pollution degree | max. 2, according to IEC 60664 | |
| Mechanical specifications | ||
| Connection type | Terminals | |
| Core cross-section | up to 2.5 mm2 | |
| Housing material | Polyamide PA 66 | |
| Degree of protection | IP20 according to EN 60529 | |
| Mass | 195 g | |
| Mounting | DIN rail mounting | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 07 ATEX 2025 X | |
| Marking | II (1) G [Ex ia Ga] IIB , II (1) D [Ex ia Da] IIIC , II 3(1)G Ex nA [ia Ga] IIB T4 Gc II 3 (1D) G Ex nA [ia IIIC Da] IIB T4 Gc I (M1) [Ex ia Ma] I | |
| Supply | ||
| Maximum safe voltage | 253 V AC | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| CSA approval | CSA 15.70016295 | |
| Control drawing | 116-B032 | |
| Approved for | Class I, Zone 2, AEx/Ex nA [ia Ga] IIB T4 Gc Class I, Zone 2, AEx/Ex nA [ia Da IIIC] IIB T4 Gc | |
| IECEx approval | IECEx PTB 09.0053X | |
| Approved for | [Ex ia Ga] IIB [Ex ia Da] IIIC Ex nA [ia Ga] IIB T4 Gc Ex nA [ia IIIC Da] IIB T4 Gc [Ex ia Ma] I | |
| Certificates and approvals | ||
| Patents | This product may be covered by the following patent: US7,687,791 | |
| General specifications | ||
|---|---|---|
| Design / Mounting | Outside installation | |
| Installed components | Binary multi-input/output R8D0-MIO-Ex12.FF* , For technical data on installed electronic component see data sheet. | |
| Fieldbus interface | ||
| Fieldbus type | FOUNDATION Fieldbus | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation | |
| Mechanical specifications | ||
| Degree of protection | IP66 | |
| Dimensions | (W x H x D) 271 x 271 x 136 mm | |
| Mounting | thru-holes Ø6.5 mm | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 07 ATEX 1061 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
| Certificate | PF 16 CERT 4011 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
| Marking | II 3(1)G Ex ic [ia Ga] IIC T4 Gc II 3(1)G Ex ec [ia Ga] IIC T4 Gc II 3(1)D Ex tc [ia Da] IIIC T135°C Dc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-31:2014 | |
| International approvals | ||
| IECEx approval | IECEx PTB 07.0036 , Zone 1 , suitable Junction Box on request IECEx PTB 09.0016 , Zone 2 , suitable Junction Box on request | |
| INMETRO | TÜV 13.1143 | |
| General specifications | ||
|---|---|---|
| Design / Mounting | Outside installation | |
| Installed components | Binary multi-input/output R8D0-MIO-Ex12.PA* , For technical data on installed electronic component see data sheet. | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS PA | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation | |
| Mechanical specifications | ||
| Degree of protection | IP66 | |
| Dimensions | (W x H x D) 271 x 271 x 136 mm | |
| Mounting | thru-holes Ø6.5 mm | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 07 ATEX 1061 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
| Certificate | PF 16 CERT 4011 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
| Marking | II 3(1)G Ex ic [ia Ga] IIC T4 Gc II 3(1)G Ex ec [ia Ga] IIC T4 Gc II 3(1)D Ex tc [ia Da] IIIC T135°C Dc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-31:2014 | |
| International approvals | ||
| IECEx approval | IECEx PTB 07.0036 , Zone 1 , suitable Junction Box on request IECEx PTB 09.0016 , Zone 2 , suitable Junction Box on request | |
| INMETRO | TÜV 13.1143 | |
Товаров: 0