Атол 30Ф не включается (заводской брак)
Валерий
14 января 2022
| Описание оборудования | ||
|---|---|---|
| Pressure relief vent | ||
| Описание оборудования | ||
|---|---|---|
| Type X & Ex px purge and pressurization system | ||
| Описание оборудования | ||
|---|---|---|
| Type X & Ex px purge and pressurization system | ||
| Описание оборудования | ||
|---|---|---|
| Type Ex px purge and pressurization system | ||
| General specifications | ||
|---|---|---|
| Distance | Transmitter "K3": 300 m (1000 ft) Transmitter "K4": 120 m (400 ft) Transmitter "K5": 200 m (650 ft), 62.5 µ multimode 400 m (1300 ft), 50.0 µ multimode | |
| Supply | ||
| Connection | Monitor: power, CAT5, fiber (LC) | |
| Power consumption | Main unit: 70 W max, 100 ... 240 VAC, 50 ... 60 Hz 20-30 VDC Transmitter "K3": PS2 power Transmitter "K4": 5 VDC @ 10 W, max Transmitter "K5": 5 VDC @ 10 W, max | |
| Indicators/operating means | ||
| Indicators | Transmitter "K3": video check LED Transmitter "K4": video check LED front panel - power Transmitter "K5": video check LED front panel - power | |
| Display | ||
| Screen diagonal | 19 inch (483 mm) | |
| Response time | Standard: 12 ms High-bright: 5 ms | |
| Resolution | 1280 x 1024 | |
| Color depth | 24 bit (16.7 M) color | |
| Contrast | 1000:1 | |
| Brightness | Standard: 450 cd/m2 (nits) High-bright: 1000 cd/m2 (nits) | |
| Reading angle | 160° in all directions | |
| Life span | back lamp life: 50,000 hrs typical half life | |
| Input devices | Transmitter "K3": VGA - HD15M/F 2 x PS2 (keyboard & mouse) 1 x RS232 (touchscreen) 1 x RJ45 (CAT5e/6) Transmitter "K4": 29-pin DVI-D 2 x USB Type A (keyboard, mouse/touchscreen) 1 x RS232 (touchscreen) 1 x RJ45 (CAT5e/6) Transmitter "K5": 29-pin DVI-D 2 x USB Type A (keyboard, mouse/touchscreen) 1 x RS232 (touchscreen) fiber optic (multimode) LC connectors | |
| Touchscreen | 5-wire resistive 5-wire hardened resistive | |
| Serial data | ||
| Baud rate | 19.2 KBd max | |
| Flow control | RTS, CTS, DTR, DSR | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 89/336/EEC | EN55022A, EN61000-6-2, EN61000-3-2, EN61000-3-3 (main unit) EN55022, EN55024, IEC61000-4-2, IEC61000-4-3, IEC61000-4.4, IEC61000-4-5, EN61000-3-2, EN61000-3-3 (KVM transmitters) | |
| Low voltage | ||
| Directive 73/23/EEC | EN60950 (KVM transmitters) | |
| Ambient conditions | ||
| Operating temperature | -20 ... 50 °C (-4 ... 122 °F) | |
| Storage temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Relative humidity | 0 ... 90% (noncondensing) | |
| Mechanical specifications | ||
| Degree of protection | Nema Type 4X | |
| Material | 304 (UNS S30400) stainless steel | |
| Mass | approx. 52.16 kg (115 lbs) Empty housing Varies with configuration | |
| Dimensions | 813 x 724 x 381 mm (32.0 x 28.5 x 15.0 inch) (sloping top) Volume: approx. 3.2 cu ft | |
| International approvals | ||
| UL approval | cULus | |
| Approved for | Class I, Division 1, Group A, B, C, D | |
| Описание оборудования | ||
|---|---|---|
| 10 inch flat panel monitor for Class I, Div 2 applications. | ||
| General specifications | ||
|---|---|---|
| Distance | Transmitter "K3": 300 m (1000 ft) Transmitter "K4": 120 m (400 ft) Transmitter "K5": 200 m (650 ft), 62.5 µ multimode 400 m (1300 ft), 50.0 µ multimode | |
| Supply | ||
| Connection | Monitor: power, CAT5, fiber (LC) | |
| Power consumption | Main unit: 48 W max, 100 ... 240 VAC, 50 ... 60 Hz 20-30 VDC Transmitter "K3": PS2 power Transmitter "K4": 5 VDC @ 10 W, max Transmitter "K5": 5 VDC @ 10 W, max | |
| Indicators/operating means | ||
| Indicators | Transmitter "K3": video check LED Transmitter "K4": video check LED front panel - power Transmitter "K5": video check LED front panel - power | |
| Display | ||
| Screen diagonal | 15 inch (381 mm) | |
| Response time | Standard: 30 ms High-bright : 25 ms | |
| Resolution | 1024 x 768 | |
| Color depth | 24 bit (16.7 M) color | |
| Contrast | Standard: 800:1 High-bright: 700:1 | |
| Brightness | Standard: 350 cd/m2 (nits) High-bright: 1200 cd/m2 (nits) | |
| Reading angle | 160° in all directions | |
| Life span | back lamp life: 50,000 hrs typical half life | |
| Input devices | Transmitter "K3": VGA - HD15M/F 2 x PS2 (keyboard & mouse) 1 x RS232 (touchscreen) 1 x RJ45 (CAT5e/6) Transmitter "K4": 29-pin DVI-D 2 x USB Type B (keyboard, mouse/touchscreen) 1 x RS232 (touchscreen) 1 x RJ45 (CAT5e/6) Transmitter "K5": 29-pin DVI-D 1 x USB Type B (keyboard, mouse/touchscreen) 1 x RS232 (touchscreen) fiber optic (multimode) LC connectors | |
| Touchscreen | 5-wire resistive 5-wire hardened resistive | |
| Keyboard | touchpad , optical trackball (50 mm) , joystick | |
| Serial data | ||
| Baud rate | 19.2 KBd max | |
| Flow control | RTS, CTS, DTR, DSR | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 89/336/EEC | EN55022A, EN61000-6-2, EN61000-3-2, EN61000-3-3 | |
| Ambient conditions | ||
| Operating temperature | -20 ... 50 °C (-4 ... 122 °F) | |
| Storage temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Relative humidity | 0 ... 90% (noncondensing) | |
| Shock resistance | 30g, 11 ms, all axis | |
| Vibration resistance | 5 ... 100 Hz 1G, 12 m/s2 | |
| Mechanical specifications | ||
| Degree of protection | Type 4X ( stainless steel ) Type 4 ( painted steel ) IP66 | |
| Material | Main enclosure: painted black steel or 316L stainless steel Main enclosure (rear cover): 6062 anodized aluminum, marine grade | |
| Installation | 100 mm ( 3.9   inch ) VESA mount | |
| Mass | Main unit: 11.3 kg (25 lb) without keyboard 16.8 kg (37 lb) with keyboard Transmitter "K3": 1.3 kg (2.9 lbs) Transmitter "K4": 0.3 kg (0.7 lbs) Transmitter "K5": 0.3 kg (0.7 lbs) | |
| Dimensions | Main enclosure: 478 x 381 x 86 mm (18.8 x 15.0 x 3.4 inch), junction box adds 43 mm (1.7 inch) to depth Keyboard enclosure: 559 x 254 x 51 mm (22.0 x 10.0 x 2.0 inch) Transmitter "K3": 198 x 99 x 36 mm (7.8 x 3.9 x 1.4 inch) Transmitter "K4": 104 x 135 x 36 mm (4.1 x 5.3 x 1.4 inch) Transmitter "K5": 104 x 135 x 36 mm (4.1 x 5.3 x 1.4 inch) | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | ||
| Group, category, type of protection | II 3G Ex ic nA IIC T4 Gc | |
| International approvals | ||
| ETL Intertek | Class I, Div. 2 Groups A, B, C, D T4 | |
| General specifications | ||
|---|---|---|
| Distance | Transmitter "K3": 300 m (1000 ft) Transmitter "K4": 120 m (400 ft) Transmitter "K5": 200 m (650 ft), 62.5 µ multimode 400 m (1300 ft), 50.0 µ multimode | |
| Supply | ||
| Connection | Monitor: power, CAT5, fiber (LC) | |
| Power consumption | Main unit: 60 W max, 100 ... 240 VAC, 50 ... 60 Hz 20-30 VDC Transmitter "K3": PS2 power Transmitter "K4": 5 VDC @ 10 W, max Transmitter "K5": 5 VDC @ 10 W, max | |
| Indicators/operating means | ||
| Indicators | Transmitter "K3": video check LED Transmitter "K4": video check LED front panel - power Transmitter "K5": video check LED front panel - power | |
| Display | ||
| Screen diagonal | 19 inch (483 mm) | |
| Response time | Standard: 12 ms High-bright: 5 ms | |
| Resolution | 1280 x 1024 | |
| Color depth | 24 bit (16.7 M) color | |
| Contrast | 1000:1 | |
| Brightness | Standard: 450 cd/m2 (nits) High-bright: 1000 cd/m2 (nits) | |
| Reading angle | 160° in all directions | |
| Life span | back lamp life: 50,000 hrs typical half life | |
| Input devices | Transmitter "K3": VGA - HD15M/F 2 x PS2 (keyboard & mouse) 1 x RS232 (touchscreen) 1 x RJ45 (CAT5e/6) Transmitter "K4": 29-pin DVI-D 2 x USB Type A (keyboard, mouse/touchscreen) 1 x RS232 (touchscreen) 1 x RJ45 (CAT5e/6) Transmitter "K5": 29-pin DVI-D 2 x USB Type A (keyboard, mouse/touchscreen) 1 x RS232 (touchscreen) fiber optic (multimode) LC connectors | |
| Touchscreen | 5-wire resistive 5-wire hardened resistive | |
| Serial data | ||
| Baud rate | 19.2 KBd max | |
| Flow control | RTS, CTS, DTR, DSR | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 89/336/EEC | EN55022A, EN61000-6-2, EN61000-3-2, EN61000-3-3 (main unit) EN55022, EN55024, IEC61000-4-2, IEC61000-4-3, IEC61000-4.4, IEC61000-4-5, EN61000-3-2, EN61000-3-3 (KVM transmitters) | |
| Low voltage | ||
| Directive 73/23/EEC | EN60950 (KVM transmitters) | |
| Ambient conditions | ||
| Operating temperature | -20 ... 50 °C (-4 ... 122 °F) | |
| Storage temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Relative humidity | 0 ... 90% (noncondensing) | |
| Mechanical specifications | ||
| Degree of protection | Nema Type 4X | |
| Material | 304 (UNS S30400) stainless steel | |
| Mass | approx. 52.16 kg (115 lbs) Empty housing Varies with configuration | |
| Dimensions | 813 x 724 x 381 mm (32.0 x 28.5 x 15.0 inch) (sloping top) Volume: approx. 3.2 cu ft | |
| International approvals | ||
| UL approval | cULus | |
| Approved for | General purpose Class I, Division 2, Groups A, B, C, and D | |
| General specifications | ||
|---|---|---|
| Type | Panel PC | |
| Hardware | ||
| Processor | 1.06 GHz Intel® Core&trade 2 Duo | |
| RAM | 2 GB | |
| Mass storage | Windows 7: 32 GByte Solid State Drive Windows XP: 16 GByte or 32 GByte Solid State Drive | |
| Supply | ||
| Rated voltage | 24 V DC ( 20 ... 30 V DC ) | |
| Power consumption | max. 85 W | |
| Indicators/operating means | ||
| Display | ||
| Screen diagonal | 48.3 cm (19 inch) | |
| Resolution | 1280 x 1024 pixels representable: 640 x 480 up to 1280 x 1024 pixels | |
| Color depth | 16 Mio. | |
| Contrast | 1000:1 | |
| Brightness | 300 cd/m2 | |
| Reading angle | 89° / 89° / 89° / 89° | |
| Life span | 50000 h | |
| Input devices | ||
| Touchscreen | Analog resistive touchscreen (optional) | |
| Keyboard | Input device combined with keyboard and optional trackball/touchpad/joystick (optional) | |
| Interface | ||
| Interface type | USB , RS-485, RS-422, RS 232, Ethernet , TTY | |
| Software | ||
| Operating system | Windows XP Professional / Windows 7 Ultimate FES | |
| Ambient conditions | ||
| Operating temperature | -10 ... 50 °C (14 ... 122 °F) (at switching on) -20 ... 50 °C (-4 ... 122 °F) (when operating) | |
| Storage temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Relative humidity | max 85 % non-condensing (48 h endurance test) | |
| Mechanical specifications | ||
| Degree of protection | IP66 | |
| Installation | Mountable on floor, wall or ceiling several mounting options (turnable/fix) available | |
| Mass | approx. 41 kg | |
| Dimensions | 537 x 457 x 158 mm (display) 590 x 700 x 470 mm (surface-mounted case) | |
| Cut out dimensions | 466 mm x 389 mm | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | BVS 07 ATEX E 008 X 2nd Edition | |
| Group, category, type of protection | II 2 G Ex e mb q [ib] IIC T4 Gb II 2 D Ex tb [ib] IIIC T85°C Db II 3 (2) G Ex e mc q [ib Gb] IIC T4 Gc II 3 (2) D Ex tc [ib Db] IIIC T85°C Dc | |
| International approvals | ||
| IECEx approval | IECEx BVS 08.0030X | |
| General specifications | ||
|---|---|---|
| Type | Remote Monitor | |
| Hardware | ||
| Processor | Intel® Atom&trade Bay Trail E3827 1.75 GHz | |
| RAM | 2 GB DDR3L | |
| Mass storage | 32 GByte industrial grade MLC SSD | |
| Supply | ||
| Power consumption | AC: 115/230 V AC, 0.7 ... 0.4 A, 50/60 Hz, max. 50 W DC:18 ... 36 V DC, 3.0 ... 1.5 A | |
| Indicators/operating means | ||
| Display | ||
| Type | Liquid Crystal Display (LCD) with LED backlight | |
| Screen diagonal | 54.61 cm (21,5 '') | |
| Resolution | 1920 x 1080 pixels (Full HD) Aspect ratio 16:9 | |
| Color depth | 24 bit (16.7 M) color | |
| Contrast | 5000:1 (typically) | |
| Brightness | 300 cd/m2 | |
| Reading angle | 175° in all directions | |
| Life span | back lamp life: 50.000 hrs typical half life , at 25 °C (77 °F) | |
| Input devices | ||
| Touchscreen | optional: projective capacitive 10 finger multi-touch, glove friendly | |
| Keyboard | Foil keyboard with different pointing device options available (see EXTA2 datasheet) | |
| Interface | ||
| Interface type | 1x 1000BASE-T LAN Ex e, 1x USB Ex e, 2x USB Ex i 1x DC/AC power in (via Power Supply Unit) 1x 1000BASE-SX Fiber Optic (multi-mode, LC connector) (alternative to 1000BASE-TX) Options for module slots A and B: 1x barcode reader interface Ex i 1x RS-232 Ex e 1x RS-485 Ex e 1x 1000BASE-T LAN Ex e | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) EN 61000-6-4:2007+A1:2011 | |
| RoHs | ||
| Directive 2011/65/EU (RoHS) | EN 50581:2012-09 | |
| Software | ||
| Operating system | VisuNet RM Shell 4.x (based on Microsoft® Windows&trade Embedded Standard 7) | |
| Ambient conditions | ||
| Operating temperature | 0 ... 50 °C (32 ... 122 °F) (normal operation) -20 ... 50 °C (-4 ... 122 °F) (after 1 hour of operation) | |
| Storage temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Relative humidity | 93% at 40°C, non-condensating, according to EN60068-2-78 | |
| Altitude | Operating altitude max. 2000 m | |
| Shock resistance | 18 shocks 15 g , 11 ms all axis, IEC 60068-2-27 | |
| Vibration resistance | 10 ... 150 Hz, +/- 0.075 mm , 1g, 10 cycles per axis according to EN60068-2-6 | |
| Mechanical specifications | ||
| Degree of protection | IP66 (individual components and entire system with housing) | |
| Material | Panel: anodized aluminum (TCU, PSU), powder coated aluminum (DPU) Bezel: stainless steel AISI 304 (1.4301) System housing: stainless steel AISI 304 (1.4301), ceramic blasted | |
| Installation | Flush-mount installation (requires customized mounting kit) Panel-mount installation into system housing with bezel Panel-mount installation into cabinet with Bezel and standard mounting kit | |
| Mass | Panel (DPU with bezel, TCU, PSU DC): approx. 23 kgPanel (DPU with bezel, TCU, PSU AC): approx. 24 kgSystem housing (AG-XX00): approx. 11 kg | |
| Dimensions | Panel (DPU with bezel, TCU, PSU DC): 625x459x120 mm Panel (DPU with bezel, TCU, PSU AC): 625x459x137 mm Panel with system housing: 625x459x173 mm | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BVS 17 ATEX E 036 X | |
| Marking | II 2G Ex eb q ib [ib] IIC T4 IP66 Gb II 2D Ex tb [ib] IIIC T85°C IP66 Db | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013, EN 60079-5:2015, EN 60079-7:2015, EN 60079-11:2012, EN 60079-31:2014 | |
| International approvals | ||
| UL approval | E492874 | |
| Approved for | Class I, Division 2, Groups A, B, C, D T4 Zone 2, Group IIC T4 Class II, Division 2, Groups F, G T4 Zone 22, Group IIIB T85 Class III Zone 22, Group IIIA T85 | |
| IECEx approval | IECEx BVS 17.0029X | |
| Approved for | Ex eb q ib [ib] IIC T4 IP66 Gb Ex tb [ib] IIIC T85°C IP66 Db | |
| Standards | IEC 60079-0:2011, IEC 60079-5:2015, IEC 60079-7:2015, IEC 60079-11:2011, IEC 60079-31:2013 | |
| Описание оборудования | ||
|---|---|---|
| 12 inch flat panel monitor for Class I, Div 2 Class II, Div 2 and Atex Zone 2 applications. | ||
| General specifications | ||
|---|---|---|
| Type | Remote Monitor | |
| Hardware | ||
| Processor | Intel® Atom&trade Bay Trail E3827 1.75 GHz | |
| RAM | 2 GB DDR3L | |
| Mass storage | 32 GByte industrial grade MLC SSD | |
| Supply | ||
| Power consumption | AC: 115/230 V AC, 0.7 ... 0.4 A, 50/60 Hz, max. 50 W DC:18 ... 36 V DC, 3.0 ... 1.5 A | |
| Indicators/operating means | ||
| Display | ||
| Type | Liquid Crystal Display (LCD) with LED backlight | |
| Screen diagonal | 54.61 cm (21,5 '') | |
| Resolution | 1920 x 1080 pixels (Full HD) Aspect ratio 16:9 | |
| Color depth | 24 bit (16.7 M) color | |
| Contrast | 5000:1 (typically) | |
| Brightness | 300 cd/m2 | |
| Reading angle | 175° in all directions | |
| Life span | back lamp life: 50.000 hrs typical half life , at 25 °C (77 °F) | |
| Input devices | ||
| Touchscreen | optional: projective capacitive 10 finger multi-touch, glove friendly | |
| Keyboard | Foil keyboard with different pointing device options available (see EXTA2 datasheet) | |
| Interface | ||
| Interface type | 1x 1000BASE-T LAN Ex e, 1x USB Ex e, 2x USB Ex i 1x DC/AC power in (via Power Supply Unit) 1x 1000BASE-SX Fiber Optic (multi-mode, LC connector) (alternative to 1000BASE-TX) Options for module slots A and B: 1x barcode reader interface Ex i 1x RS-232 Ex e 1x RS-485 Ex e 1x 1000BASE-T LAN Ex e | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) EN 61000-6-4:2007+A1:2011 | |
| RoHs | ||
| Directive 2011/65/EU (RoHS) | EN 50581:2012-09 | |
| Software | ||
| Operating system | VisuNet RM Shell 4.x (based on Microsoft® Windows&trade Embedded Standard 7) | |
| Ambient conditions | ||
| Operating temperature | 0 ... 50 °C (32 ... 122 °F) (normal operation) -20 ... 50 °C (-4 ... 122 °F) (after 1 hour of operation) | |
| Storage temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Relative humidity | 93% at 40°C, non-condensating, according to EN60068-2-78 | |
| Altitude | Operating altitude max. 2000 m | |
| Shock resistance | 18 shocks 15 g , 11 ms all axis, IEC 60068-2-27 | |
| Vibration resistance | 10 ... 150 Hz, +/- 0.075 mm , 1g, 10 cycles per axis according to EN60068-2-6 | |
| Mechanical specifications | ||
| Degree of protection | IP66 (individual components and entire system with housing) | |
| Material | Panel: anodized aluminum (TCU, PSU), powder coated aluminum (DPU) Bezel: stainless steel AISI 304 (1.4301) System housing: stainless steel AISI 304 (1.4301), ceramic blasted | |
| Installation | Flush-mount installation (requires customized mounting kit) Panel-mount installation into system housing with bezel Panel-mount installation into cabinet with Bezel and standard mounting kit | |
| Mass | Panel (DPU with bezel, TCU, PSU DC): approx. 17.5 kg Panel (DPU with bezel, TCU, PSU AC): approx. 18 kg System housing: approx. 11 kg | |
| Dimensions | Panel (DPU with bezel, TCU, PSU DC): 625x459x120 mm Panel (DPU with bezel, TCU, PSU AC): 625x459x137 mm Panel with system housing: 625x459x173 mm | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BVS 17 ATEX E 036 X | |
| Marking | II 3G Ex ec [ib] q IIC T4 IP66 Gc II 3D Ex tc [ib] IIIC T85 °C IP66 Dc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013, EN 60079-7:2015, EN 60079-11:2012, EN 60079-31:2014 | |
| International approvals | ||
| UL approval | E492874 | |
| Approved for | Class I, Division 2, Groups A, B, C, D T4 Zone 2, Group IIC T4 Class II, Division 2, Groups F, G T4 Zone 22, Group IIIB T85 Class III Zone 22, Group IIIA T85 | |
| IECEx approval | IECEx BVS 17.0029X | |
| Approved for | Ex ec [ib] q IIC T4 IP66 Gc Ex tc [ib] IIIC T85 °C IP66 Dc | |
| Standards | IEC 60079-0:2011, IEC 60079-7:2015, IEC 60079-11:2011, IEC 60079-31:2013 | |
| General specifications | ||
|---|---|---|
| Type | Direct Monitor | |
| Supply | ||
| Power supply | 24 V DC | |
| Power consumption | 40 W | |
| Indicators/operating means | ||
| Display | ||
| Type | TFT, LCD, High Color (19 bit) | |
| Screen diagonal | 48.3 cm (19 inch) | |
| Resolution | 1280 x 1024 Pixel | |
| Color depth | 16.7 Mio. | |
| Brightness | 300 cd/m2 | |
| Input devices | Analog resistive touchscreen (optional) , Keyboard with integrated mouse functionality: optical trackball/touchpad/joystick versions available | |
| Interface | ||
| Interface type | VGA or DVI | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 50 °C (32 ... 122 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP65 | |
| Surface quality | Ra 0.8 µm | |
| Mounting type | slim line housing several mounting types (pedestal, wall bracket, wall arm - each turnable or fix) available | |
| Mass | approx. 12 kg | |
| Dimensions | 568 mm x 450 mm x 73 mm | |
| Описание оборудования | ||
|---|---|---|
| 10 inch flat panel monitor for general purpose applications. | ||
| General specifications | ||
|---|---|---|
| Distance | Transmitter "K3": 300 m (1000 ft) Transmitter "K4": 120 m (400 ft) Transmitter "K5": 200 m (650 ft), 62.5 µ multimode 400 m (1300 ft), 50.0 µ multimode | |
| Supply | ||
| Connection | Monitor: power, CAT5, fiber (LC) | |
| Power consumption | Main unit: 48 W max, 100 ... 240 VAC, 50 ... 60 Hz 20-30 VDC Transmitter "K3": PS2 power Transmitter "K4": 5 VDC @ 10 W, max Transmitter "K5": 5 VDC @ 10 W, max | |
| Indicators/operating means | ||
| Indicators | Transmitter "K3": video check LED Transmitter "K4": video check LED front panel - power Transmitter "K5": video check LED front panel - power | |
| Display | ||
| Screen diagonal | 15 inch (381 mm) | |
| Response time | Standard: 30 ms High-bright : 25 ms | |
| Resolution | 1024 x 768 | |
| Color depth | 24 bit (16.7 M) color | |
| Contrast | Standard: 800:1 High-bright: 700:1 | |
| Brightness | Standard: 350 cd/m2 (nits) High-bright: 1200 cd/m2 (nits) | |
| Reading angle | 160° in all directions | |
| Life span | back lamp life: 50,000 hrs typical half life | |
| Input devices | Transmitter "K3": VGA - HD15M/F 2 x PS2 (keyboard & mouse) 1 x RS232 (touchscreen) 1 x RJ45 (CAT5e/6) Transmitter "K4": 29-pin DVI-D 2 x USB Type B (keyboard, mouse/touchscreen) 1 x RS232 (touchscreen) 1 x RJ45 (CAT5e/6) Transmitter "K5": 29-pin DVI-D 1 x USB Type B (keyboard, mouse/touchscreen) 1 x RS232 (touchscreen) fiber optic (multimode) LC connectors | |
| Touchscreen | 5-wire resistive 5-wire hardened resistive | |
| Keyboard | touchpad , optical trackball (50 mm) , joystick | |
| Serial data | ||
| Baud rate | 19.2 KBd max | |
| Flow control | RTS, CTS, DTR, DSR | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 89/336/EEC | EN55022A, EN61000-6-2, EN61000-3-2, EN61000-3-3 | |
| Ambient conditions | ||
| Operating temperature | -20 ... 50 °C (-4 ... 122 °F) | |
| Storage temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Relative humidity | 0 ... 90% (noncondensing) | |
| Shock resistance | 30g, 11 ms, all axis | |
| Vibration resistance | 5 ... 100 Hz 1G, 12 m/s2 | |
| Mechanical specifications | ||
| Degree of protection | Type 4X ( stainless steel ) Type 4 ( painted steel ) IP66 | |
| Material | Main enclosure: painted black steel or 316L stainless steel Main enclosure (rear cover): 6062 anodized aluminum, marine grade | |
| Installation | 100 mm ( 3.9   inch ) VESA mount | |
| Mass | Main unit: 11.3 kg (25 lb) without keyboard 16.8 kg (37 lb) with keyboard Transmitter "K3": 1.3 kg (2.9 lbs) Transmitter "K4": 0.3 kg (0.7 lbs) Transmitter "K5": 0.3 kg (0.7 lbs) | |
| Dimensions | Main enclosure: 478 x 381 x 86 mm (18.8 x 15.0 x 3.4 inch), junction box adds 43 mm (1.7 inch) to depth Keyboard enclosure: 559 x 254 x 51 mm (22.0 x 10.0 x 2.0 inch) Transmitter "K3": 198 x 99 x 36 mm (7.8 x 3.9 x 1.4 inch) Transmitter "K4": 104 x 135 x 36 mm (4.1 x 5.3 x 1.4 inch) Transmitter "K5": 104 x 135 x 36 mm (4.1 x 5.3 x 1.4 inch) | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | ||
| Group, category, type of protection | II 3G Ex ic nA IIC T4 Gc | |
| International approvals | ||
| ETL Intertek | Class I, Div. 2 Groups A, B, C, D T4 | |
| Описание оборудования | ||
|---|---|---|
| Environmental purge for nonhazardous dusty/dirty areas | ||
| Functional safety related parameters | ||
|---|---|---|
| Safety Integrity Level (SIL) | SIL 3 | |
| Supply | ||
| Connection | SL1: 1a, 1b(-) 2a, 2b(+) | |
| Rated voltage | 20.4 ... 30 V DC via Termination Board | |
| Rated current | 28 mA at 24 V , RS-485, quiescent current | |
| Power dissipation | 0.7 W at 24 V | |
| HART signal channels (non-intrinsically safe) | ||
| Number of channels | 32 | |
| Conformity | HART field device input (revision 5 to 7) | |
| Signal range | 0.12 Vpp < signal < 1.5 Vpp | |
| Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) | |
| Terminating resistor | external 230 ... 500 &Omega standard (up to 1000 &Omega possible) | |
| Output voltage | &ge 400 mV ss (with the terminator resistance specified above) | |
| Output resistance | 100 &Omega or smaller, capacitive coupling | |
| DC isolation | dual capacitor each channel | |
| Common mode voltage | up to 30 V | |
| Input impedance | > 5 k&Omega , according to HART specification | |
| Input voltage range | 0.12 ... 1.5 V ss | |
| Common mode voltage | max. 30 V | |
| Differential mode clamping | ± 5.2 V , for transient or AC signals | |
| Common mode clamping | ± 10 V , for transient or AC signals | |
| Carrier detect level | signal > 0.12 Vpp, carrier detection activated signal < 0.08 Vpp, carrier detection not activated | |
| Transmit amplitude | 200 &Omega load, 0.43 Vpp < signal < 0.49 Vpp 500 &Omega load, 1.1 Vpp < signal < 1.2 Vpp | |
| Device type | DC isolated bus device | |
| Impedance | high impedance | |
| Data link type | HART primary and secondary | |
| Field multi point support | option available upon request | |
| Interface | ||
| Transfer rate | 9600 MBit/s, 19200 MBit/s or 38400 MBit/s, selectable via switch | |
| Address | 1 ... 31 , adjustable via DIP switch | |
| Type | RS-485 , differential pair and grounding | |
| Topology | multi point, master/slave connection | |
| Indicators/settings | ||
| Display elements | LEDs LED PWR ON (power supply), one green LED LED HART TX (HART transmission), one yellow LED LED FAULT (lead fault), one red LED | |
| Control elements | DIP switches at the housing side for: - unit slave address - baud rate - test mode on/off | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 140 g | |
| Dimensions | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) | |
| Mounting | on Termination Board | |
| Data for application in connection with hazardous areas | ||
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| International approvals | ||
| CSA approval | 1256050 | |
| Approved for | Class I, Division 2, Groups A, B, C, D Class I, Zone 2, IIC | |
| Functional safety related parameters | ||
|---|---|---|
| Safety Integrity Level (SIL) | SIL 3 | |
| Supply | ||
| Connection | terminals 17+, 18- | |
| Rated voltage | 20 ... 32 V DC typical at 100 mA | |
| Power consumption | max. 3 W | |
| HART signal channels (non-intrinsically safe) | ||
| Conformity | HART field device input (revision 5 to 7) | |
| Connection | 26-pin flat cable for analog connections 14-pin flat cable for master-slave connection between KFD2-HMM-16 and KFD0-HMS-16 | |
| Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) | |
| Terminating resistor | external 230 ... 500 &Omega standard (up to 1000 &Omega possible) | |
| Output voltage | &ge 400 mV ss (with the terminator resistance specified above) | |
| Output resistance | 100 &Omega or smaller, capacitive coupling | |
| Input impedance | according to HART specification | |
| Input voltage range | 0.08 ... 4 V ss typ. ± 5.2 V as local reference | |
| Interface | ||
| Transfer rate | 9600, 19200, or 38400 Bit/s (selectable with DIL switch (2 and 3) by the user) | |
| Type | RS-485 , 2-wire multidrop | |
| Address selection | One of 31 possible addresses selectable per DIL switch (4 ... 8) | |
| Indicators/settings | ||
| Control elements | DIP-switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 250 g | |
| Dimensions | 40 x 107 x 115 mm (1.6 x 4.2 x 4.5 inch) , housing type C1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 07 CERT 1143 X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| Functional safety related parameters | ||
|---|---|---|
| Safety Integrity Level (SIL) | SIL 3 | |
| Supply | ||
| Connection | via 14-channel flat cable form master KFD2-HMM-16 | |
| HART signal channels (non-intrinsically safe) | ||
| Conformity | HART field device input (revision 5 to 7) | |
| Connection | 26-pin flat cable for analog connections 14-pin flat cable for master-slave connection between KFD2-HMM-16 and KFD0-HMS-16 | |
| Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) | |
| Terminating resistor | external 230 ... 500 &Omega standard (up to 1000 &Omega possible) | |
| Output voltage | &ge 400 mV ss (with the terminator resistance specified above) | |
| Output resistance | 100 &Omega or smaller, capacitive coupling | |
| Input impedance | according to HART specification | |
| Input voltage range | 0.08 ... 4 V ss typ. ± 5.2 V as local reference | |
| Indicators/settings | ||
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 100 g | |
| Dimensions | 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) , housing type B1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 07 CERT 1143 X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| Описание оборудования | ||
|---|---|---|
| 230 V AC | ||
| HART signal channels (non-intrinsically safe) | ||
|---|---|---|
| Load resistor | 220 &Omega , switchable on | |
| Interface | ||
| Type | multiplexer connection : 26-pin NFP-26A (Yamaichi) | |
| Signal lines | ||
| Rated current | max. 30 mA per channel | |
| Indicators/settings | ||
| DIP switch | selection of operating mode: - ON: without load resistor - OFF: with load resistor | |
| Factory setting | DIP switches S1 and S2: ON | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 50 °C (32 ... 122 °F) | |
| Storage temperature | -15 ... 50 °C (5 ... 122 °F) | |
| Relative humidity | &le 93 % non-condensing | |
| Shock resistance | 15 g , 11 ms | |
| Vibration resistance | 1 g , 10 ... 150 Hz | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | ||
| Field side | screw terminals , green | |
| Control side | screw terminals , green HART : 1 x IDC plug, 26-pin | |
| Core cross-section | screw terminals: 0.25 ... 1.5 mm2 (24 ... 16 AWG) | |
| Mass | approx. 200 g | |
| Dimensions | 110 x 125 x 67 mm (4.3 x 4.9 x 2.6 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 55 °C (-4 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: fixed screw terminals control side: fixed screw terminals RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 222 x 122 x 79 mm (8.7 x 4.8 x 3.1 inch) with HiDMux2700: 222 x 122 x 208 mm (8.7 x 4.8 x 8.2 inch) | |
| Mounting | DIN rail mounting | |
| Supply | ||
|---|---|---|
| Rated voltage | 8.2 V ± 2 V | |
| Current consumption | < 1.0 mA unswitched (de-energized at the bottom), > 2.2 mA switched (floated up at the top) | |
| Reverse polarity protection | yes | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 60947-5-2:2007+A1:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Application | ||
| Description | Proximity switch with operation ball | |
| Function and system design | ||
| Equipment architecture | A measuring system consists of a float switch LFL1-**-N and a transformer isolated barrier, e. g. KFD2-SR2-Ex1.W. | |
| Operating conditions | ||
| Installation conditions | ||
| Installation instructions | range of application and minimum length between mounting and float: - PVC version: &ge 50 mm (2 inch), preferred for water - PUR version: &ge 100 mm (4 inch), preferred for fuels, heating oils, oily fluids - CSM/CM version: &ge 100 mm (4 inch), preferred for many acids and lyes mounting: - The float switch is mounted either from sidewards through a cable gland &ge G1A into the vessel or - by means of a counter weight or rods (e. g. float switch combination) from the top. The pivot of the cable should always be horizontal. | |
| Process conditions | ||
| Process pressure (static pressure) | sleeve design: &le 3 bar at 20 °C (68 °F) ball design: &le 2 bar at 20 °C (68 °F) | |
| Density | sleeve design: &ge 0.8 g/cm3 ball design: &ge 0.6 g/cm3 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Altitude | &le 2000 m above MSL | |
| Mechanical specifications | ||
| Degree of protection | IP68 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | TÜV 99 ATEX 1407 | |
| Group, category, type of protection | II 2G Ex ia IIB T5 | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 | |
| Mechanical construction | ||
| Material | float: PP (Polypropylene) cable: - PVC version: PVC cable, highly flexible (2 x 0.75 mm2) - PUR version: PUR cable, highly flexible (2 x 0.50 mm2) - CSM/CM version: CSM/CM cable (chlorinated polyethylene, (2 x 0.75 mm2)) | |
| Conformity | ||
|---|---|---|
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 50 °C (-4 ... 122 °F) | |
| Storage temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP66 | |
| Connection | 1 cable gland M16 x 1.5 for cable diameter 5,5 ... 10 mm, blue color 1 M12 x 5 connector for connecting a barcode reader type PSCAN-D 1 PE bolt M6 | |
| Material | Housing: antistatic glass reinforced polyester, black color Holder for barcode reader: stainless steel 1.4301 (304) M12 cable gland: stainless steel 1.4301 (304) PE bolt: brass | |
| Mass | approx. 2000 g | |
| Dimensions | 155 x 145 x 217 mm | |
| Data for application in connection with hazardous areas | ||
| Statement of conformity | ||
| Group, category, type of protection, temperature class | simple apparatus for use in gas/dust atmosphere according to EN 60079-11, temperature class T4 | |
| Voltage | 30 V | |
| Current | 500 mA | |
| Power | 2 W | |
| General information | ||
| Supplementary information | Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power Rail or terminals 23+, 24- | |
| Rated voltage | 19 ... 30 V DC | |
| Rated current | approx. 120 mA at 24 V DC | |
| Power dissipation | 2.3 W | |
| Power consumption | 2.9 W | |
| HART signal channels (intrinsically safe) | ||
| Conformity | HART field device input (revision 5 to 7) | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3, 4, 5, 6 | |
| Open circuit voltage/short-circuit current | typ. 24 V / 28 mA | |
| Input resistance | 250 &Omega , 5 % (terminals 2, 3 and with jumper on 5, 6) | |
| Available voltage | &ge 15.5 V at 20 mA, short-circuit protected | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 7, 8, 9 , output II: terminals 13, 14, 15 , output III: terminals 19, 20, 21 | |
| Output signal | analog | |
| Current range | 4 ... 20 mA , (source or sink mode) | |
| Load | max. 650 &Omega , source mode | |
| Voltage range | 5 ... 30 V , sink mode from external supply | |
| Fault signal | downscale I &le 2 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) or hold measurement value | |
| Other outputs | HART communicator on terminals 22, 24 | |
| Collective error message | Power Rail and LED red | |
| Indicators/settings | ||
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons via PACTware | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BASEEFA 07 ATEX 0174 | |
| Marking | II (1)GD [Ex ia] IIC, [Ex iaD] | |
| Certificate | PF 07 CERT 1142 X | |
| Marking | II 3G Ex nA II T4 X | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0129 | |
| IECEx approval | ||
| IECEx certificate | IECEx BAS 07.0047 | |
| IECEx marking | [Ex ia] IIC , [Ex iaD] | |
| Supply | ||
|---|---|---|
| Rated voltage | 3.6 V DC , battery operated | |
| Power dissipation/power consumption | < 0.09 W | |
| Input | ||
| Connection | terminals 1, 2, 3, 4 | |
| RTD | type Pt100, Pt1000 (IEC 751: 1995 GOST: alpha = 0.391) | |
| Connection | 2-wire: 2 sensors, 3- or 4-wire: 1 sensor | |
| Lead resistance | max. 10 &Omega | |
| Measuring circuit monitoring | sensor breakage | |
| Thermocouples | type E, J, K, T (IEC 584-1) | |
| Cold junction compensation | internal , external | |
| Measuring circuit monitoring | sensor breakage | |
| Measurement range | type K: -270 ... 1370 °C type T: -270 ... 400 °C type E: -270 ... 1000 °C type J: -210 ... 1200 °C | |
| Resistor | ||
| Measurement range | 0 ... 500 &Omega , 0 ... 4000 &Omega | |
| Voltage | mV Input | |
| Measurement range | -100 ... 100 mV , 0 ... 300 mV | |
| Input resistance | &ge 1 M&Omega | |
| Output | ||
| Output variables | PV: input 1 (°C, &Omega, mV) SV: input 2 (°C, &Omega, mV) TV: CJC temperature (°C) estimated battery life (days) battery voltage (volts) residual battery capacity (%) | |
| Transfer characteristics | ||
| Accuracy | - internal cold junction compensation error ± 1,5 °C (typ. acc. to IEC 61298-3) - external cold junction compensation error ± 1 °C (typ.) - resolution error < 0.1 °C - accuracy TC ± 20 µV - accuracy RTD: ± 100 m&Omega | |
| Indicators/settings | ||
| Parameter assignment | - sampling period: 1, 2, 5, 10, 30 seconds or 1, 2, 5, 10, 30, 60 minutes - transmit power: configurable 0 dBm or 10 dBm (EIRP) - sensor type - mapping of input measuring values 1 and 2 into primary variable (PV) and secondary variable (SV) - publishing of up to three messages from the device, transmission rate selectable from 4 seconds to 60 minutes | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2004/108/EC | EN 61326-1:2006 | |
| Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
| Directive 99/5/EC | ETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001 | |
| FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Accuracy | IEC 61298-3 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -20 ... 70 °C (-4 ... 158 °F) | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
| Mechanical specifications | ||
| Degree of protection | IP65 | |
| Mass | approx. 1000 g | |
| Dimensions | 77 x 129 x 177 mm (3 x 5.08 x 6.97 inch) | |
| Mounting | panel or pole mounting | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | IMQ 09 ATEX 008X | |
| Group, category, type of protection | II 2(1)G Ex ia [ia] IIC T4 | |
| Directive conformity | ||
| Directive 94/9/EC | EN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007 | |
| International approvals | ||
| FM approval | CoC 3042534 | |
| IECEx approval | IECEx INE 09.0025X | |
| Approved for | Ex ia IIC T4 | |
| Accessories | ||
| Designation | battery W-BAT-B1-Li mandatory for use in connection with hazardous areas (order separately) Mounting set W-ACC-F7MK External cold junction compensation W-ACC-CJC | |
| Описание оборудования | ||
|---|---|---|
| Industrial Box Thin Client | ||
| Mechanical specifications | ||
|---|---|---|
| Material | 6061 aluminum with clear anodized coating | |
| Mass | 0.564 kg | |
| General specifications | ||
|---|---|---|
| Sensing range | 0.3 ... 4 m , with fluids | |
| Transducer frequency | approx. 85 kHz | |
| Indicators/operating means | ||
| LED green | Power on | |
| LED red | 2 Hz flashing: error | |
| Electrical specifications | ||
| Operating voltage | 20 ... 30 V DC , ripple 10 %SS | |
| Power consumption | &le 1200 mW | |
| Output | ||
| Output type | 1 analog output 4 ... 20 mA, RL &le 500 Ohm, error &ge 21 mA 1 voltage output 0 ... 10 V, RL &ge 1000 Ohm, error &ge 10.5 V | |
| Resolution | 2 mm | |
| Deviation of the characteristic curve | 0.5 % of upper limit of measuring range | |
| Approvals and certificates | ||
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP65 | |
| Connection | 5-pin V15 (M12 x 1) connector | |
| Material | ||
| Housing | PBT, polypropylene | |
| Transducer | PTFE (diaphragm surface) | |
| Mass | 220 g | |
| Mounting | G1½A connection | |
| General specifications | ||
|---|---|---|
| Design / Mounting | Cabinet installation | |
| Electrical specifications | ||
| Rated voltage | 33 V | |
| Rated current | 500 mA | |
| Voltage protection level | ||
| Line/Line | max. 58 V category C1/C2 8/20µsec max. 50 V category C3 1kV/µsec max. 51 V category B2 10/700µsec max. 55 V category D1 10/350µsec | |
| Line/Earth | max. 1400 V category C1/C2 8/20µsec max. 1100 V category C1/C2 1kV/µsec max. 1000 V category B2 10/700µsec max. 1300 V category D1 10/350µsec | |
| Screen/Shield directly grounded | max. 25 V category C1/C2 8/20µsec max. 20 V category D1 10/350µsec | |
| Screen/Shield indirectly grounded (via GDT) | max. 700 V category C1/C2 8/20µsec max. 600 V category C3 1kV/µsec max. 500 V category B2 10/700µsec max. 600 V category D1 10/350µsec | |
| Reaction time | ||
| Line/Line | max. 1 ns | |
| Line/Earth | max. 100 ns | |
| Screen/Shield-Earth | max. 100 ns | |
| Overstressed fault mode | acc. IEC 61643-21 line inoperable mode 3 lines 1 and 2 at 15,5kA (8/20µsec) lines 3 and 4 at 30kA (8/20µsec) | |
| Series resistance in line | 1 &Omega +/- 5 % | |
| Impulse durability | ||
| Per line | 1 kA category D1 10/350µsec , 5 kA category C1/C2 8/20µsec | |
| Screen/Shield directly grounded | 5 kA category D1 10/350µsec | |
| Screen/Shield indirectly grounded (via GDT) | 4 kA category D1 10/350µsec , 10 kA category C1/C2 8/20µsec | |
| Capacitance | ||
| Line/Line | 800 pF | |
| Line/Earth | 16 pF | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Standard conformity | ||
| Degree of protection | IEC 60529 | |
| Fieldbus standard | IEC 61158-2 | |
| Climatic conditions | IEC 60721 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Surge protection | IEC 61643-21 | |
| Ambient conditions | ||
| Ambient temperature | -50 ... 80 °C (-58 ... 176 °F) | |
| Storage temperature | -50 ... 85 °C (-58 ... 185 °F) | |
| Relative humidity | &le 95 % non-condensing | |
| Shock resistance | 15 g 11 ms | |
| Vibration resistance | 1 g , 10 ... 150 Hz | |
| Mechanical specifications | ||
| Connection type | screw terminals | |
| Core cross-section | flexible wire 2.5 mm2 solid wire max. 4 mm2 | |
| Housing material | Polyamide PA 6.6 | |
| Degree of protection | IP20 | |
| Mass | Protection Module 20 g , base module 40 g | |
| Mounting | 35 mm DIN mounting rail | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | KEMA 09 ATEX 0191 X | |
| Marking | II 2(1)G Ex ia [ia Ga] IIC T4/T5/T6 Gb | |
| Voltage | 30 V | |
| Current | 500 mA | |
| Internal capacitance | negligible 0 nF | |
| Internal inductance | negligible 0 µH | |
| Certificate | KEMA 09 ATEX 0190 X | |
| Marking | II 3G Ex ic IIC T4/T5/T6 Gc , II 3G Ex nA IIC T4/T5/T6 Gc | |
| Voltage | 33 V | |
| Current | 500 mA | |
| Internal capacitance | negligible 0 nF | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 | |
| International approvals | ||
| CSA approval | CSA 2437472 | |
| Control drawing | 116-0361 | |
| Approved for | Class I, Zone 1, AEx/Ex ia IIC T4...T6, Class I, Zone 2, AEx nC IIC T4...T6, Class I, Zone 2, Ex nL IIC T4...T6, Class I, Zone 2, AEx/Ex nA IIC T4...T6 Class I Div. 1, GP A, B, C, D T4...T6, Class I Div. 2, GP A, B, C, D T4...T6, Class I Div. 2, GP A, B, C, D T4...T6 | |
| IECEx approval | IECEx KEM 09.0088X | |
| Approved for | Ex ia [ia Ga] IIC T4/T5/T6 Gb , Ex ic IIC T4/T5/T6 Gc , Ex nA IIC T4/T5/T6 Gc | |
| Certificates and approvals | ||
| Marine approval | pending | |
Товаров: 0