| General specifications | ||
|---|---|---|
| Design / Mounting | Cabinet installation | |
| Electrical specifications | ||
| Rated voltage | 33 V | |
| Rated current | 500 mA | |
| Voltage protection level | ||
| Line/Line | max. 58 V category C1/C2 8/20µsec max. 50 V category C3 1kV/µsec max. 51 V category B2 10/700µsec max. 55 V category D1 10/350µsec | |
| Line/Earth | max. 1400 V category C1/C2 8/20µsec max. 1100 V category C1/C2 1kV/µsec max. 1000 V category B2 10/700µsec max. 1300 V category D1 10/350µsec | |
| Screen/Shield directly grounded | max. 25 V category C1/C2 8/20µsec max. 20 V category D1 10/350µsec | |
| Screen/Shield indirectly grounded (via GDT) | max. 700 V category C1/C2 8/20µsec max. 600 V category C3 1kV/µsec max. 500 V category B2 10/700µsec max. 600 V category D1 10/350µsec | |
| Reaction time | ||
| Line/Line | max. 1 ns | |
| Line/Earth | max. 100 ns | |
| Screen/Shield-Earth | max. 100 ns | |
| Overstressed fault mode | acc. IEC 61643-21 line inoperable mode 3 lines 1 and 2 at 15,5kA (8/20µsec) lines 3 and 4 at 30kA (8/20µsec) | |
| Series resistance in line | 1 &Omega +/- 5 % | |
| Impulse durability | ||
| Per line | 1 kA category D1 10/350µsec , 5 kA category C1/C2 8/20µsec | |
| Screen/Shield directly grounded | 5 kA category D1 10/350µsec | |
| Screen/Shield indirectly grounded (via GDT) | 4 kA category D1 10/350µsec , 10 kA category C1/C2 8/20µsec | |
| Capacitance | ||
| Line/Line | 800 pF | |
| Line/Earth | 16 pF | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Standard conformity | ||
| Degree of protection | IEC 60529 | |
| Fieldbus standard | IEC 61158-2 | |
| Climatic conditions | IEC 60721 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Surge protection | IEC 61643-21 | |
| Ambient conditions | ||
| Ambient temperature | -50 ... 80 °C (-58 ... 176 °F) | |
| Storage temperature | -50 ... 85 °C (-58 ... 185 °F) | |
| Relative humidity | &le 95 % non-condensing | |
| Shock resistance | 15 g 11 ms | |
| Vibration resistance | 1 g , 10 ... 150 Hz | |
| Mechanical specifications | ||
| Connection type | screw terminals | |
| Core cross-section | flexible wire 2.5 mm2 solid wire max. 4 mm2 | |
| Housing material | Polyamide PA 6.6 | |
| Degree of protection | IP20 | |
| Mass | Protection Module 20 g , base module 40 g | |
| Mounting | 35 mm DIN mounting rail | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | KEMA 09 ATEX 0191 X | |
| Marking | II 2(1)G Ex ia [ia Ga] IIC T4/T5/T6 Gb | |
| Voltage | 30 V | |
| Current | 500 mA | |
| Internal capacitance | negligible 0 nF | |
| Internal inductance | negligible 0 µH | |
| Certificate | KEMA 09 ATEX 0190 X | |
| Marking | II 3G Ex ic IIC T4/T5/T6 Gc , II 3G Ex nA IIC T4/T5/T6 Gc | |
| Voltage | 33 V | |
| Current | 500 mA | |
| Internal capacitance | negligible 0 nF | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 | |
| International approvals | ||
| CSA approval | CSA 2437472 | |
| Control drawing | 116-0361 | |
| Approved for | Class I, Zone 1, AEx/Ex ia IIC T4...T6, Class I, Zone 2, AEx nC IIC T4...T6, Class I, Zone 2, Ex nL IIC T4...T6, Class I, Zone 2, AEx/Ex nA IIC T4...T6 Class I Div. 1, GP A, B, C, D T4...T6, Class I Div. 2, GP A, B, C, D T4...T6, Class I Div. 2, GP A, B, C, D T4...T6 | |
| IECEx approval | IECEx KEM 09.0088X | |
| Approved for | Ex ia [ia Ga] IIC T4/T5/T6 Gb , Ex ic IIC T4/T5/T6 Gc , Ex nA IIC T4/T5/T6 Gc | |
| Certificates and approvals | ||
| Marine approval | pending | |
| General specifications | ||
|---|---|---|
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 1 | |
| Suitable components | protection module M-LB-1.150.M | |
| Electrical specifications | ||
| Nominal voltage | 120 V AC | |
| Maximum continuous operating voltage | max. 150 V AC max. 200 V DC | |
| Temporary over-voltage | 175 V / 5 s (TOV withstand) | |
| Nominal discharge current (8/20 µs) | 15 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Voltage protection level | max. 0.7 kV max. 0.55 kV at 5 kA | |
| Reaction time | max. 25 ns | |
| Short-circuit-proof | 50 kA eff | |
| Overcurrent protection | max. 125 A gG , mains-side | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 240 g | |
| Dimensions | 18 x 90 x 73 mm (0.7 x 3.6 x 2.9 inch) (1 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Описание оборудования | ||
|---|---|---|
| &lambda/4 surge protection, N socket to N socket | ||
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC SELV/PELV | |
| Power consumption | < 5 W | |
| External bus | ||
| Connection | screw terminals for - 0.2 ... 4 mm2 (rigid wire) - 0.2 ... 2.5 mm2 (flexible wire) | |
| Interface 1 | Ethernet 10 BASE-T/100 BASE-TX , full galvanic isolation | |
| Protocol | HART UDP, MODBUS TCP | |
| Interface 2 | RS-485 | |
| Protocol | HART, MODBUS RTU | |
| Transfer rate | max. 115 kBit/s | |
| Galvanic isolation | ||
| Interface/interface | basic insulation according to IEC 61140, rated insulation voltage 50 Veff | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
| Directive 2014/53/EU | EN 300328: V2.1.1 EN 301489-17: V1.3.2 | |
| FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
| Mechanical specifications | ||
| Degree of protection | IP66/IP67 | |
| Mass | approx. 1 kg | |
| Dimensions | 258 mm x 114 mm x 84 mm without antenna and cable glands | |
| Mounting | panel mounting | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | FM 12 ATEX 0061 | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | Coc3042646 | |
| Approved for | NI Class I, Div. 2, GPS A-D NI Class II, Class III, Div. 2, GPS E-G | |
| IECEx approval | IECEx FMG 12.0002 | |
| Approved for | Ex nA IIC T4 Gc , Ex nAc T4 | |