Атол 30Ф не включается (заводской брак)
Валерий
14 января 2022
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 0.45 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| temperature input | ||
| Number of channels | 1 | |
| Suitable field devices | ||
| Field device | resistance thermometer | |
| Field device [3] | slide-wire sensors | |
| Field device interface | ||
| Connection | 2-wire sensor | |
| Connection [2] | 3-wire sensor | |
| Connection [3] | 4-wire sensor | |
| Connection | 2-wire connection: 5, 6 3-wire connection: 1, 5, 6 4-wire connection: 1, 2, 5, 6 | |
| Measurement range | 10 ... 400 &Omega (500 &Omega incl. line resistance) | |
| Slide-wire sensor | 10 ... 400 &Omega | |
| Measuring current | 200 µA | |
| Smallest span | 20 &Omega for 0.1 % accuracy | |
| Linearity error | 0.1 % | |
| Conversion time | max. 20 ms without LFD max. 150 ms with LFD | |
| Lead resistance | max. 50 &Omega per strand | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Short-circuit | < 10 &Omega | |
| Open-circuit | > 1 k&Omega | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Status LED (1) red: line fault | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 90 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ic] IIC T4 Gc | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 2 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
| Power consumption | 0.7 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Input | ||
| Digital signals (active) | ||
| Switching point: ON | ||
| Digital input | ||
| Number of channels | 8 | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection | channel I: 1+, 2- channel II: 3+, 4- channel III: 5+, 6- channel IV: 7+, 8- channel V: 9+, 10- channel VI: 11+, 12- channel VII: 13+, 14- channel VIII: 15+, 16- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 1 ms | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative humidity | 95 % non-condensing | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 750 g | |
| Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 97 ATEX 1074 U | |
| Marking | II 2(1) G Ex d [ia Ga] IIC Gb II (1) D [Ex ia Da] IIIC | |
| Input | ||
| Voltage | 14.9 V | |
| Current | 15.7 mA | |
| Power | 58.2 mW (linear characteristic) | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PTB 97 ATEX 1075 PTB 97 ATEX 1074 U | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 1.2 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 8 | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection | Terminals 1+, 2-, 3+, 4-, 5+, 6-, 7+, 8-, 9+, 10-, 11+, 12-, 13+,14-, 15+, 16- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 15 ms | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-8) red: line fault (lead breakage or short circuit) , yellow: signal (per channel) | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with spring terminal (0.14 ... 0.5 mm2) | |
| Mass | approx. 90 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | EXA 13 ATEX 0036X | |
| Marking | II 3(1) G Ex nA [ia Ga] IIC T4 Gc I (M1) [Ex ia Ma] I II (1) D [Ex ia Da] IIIC | |
| Input | ||
| Voltage | 10 V | |
| Current | 12 mA | |
| Power | 30 mW (linear characteristic) | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2011 EN 60079-11:2011 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | EXA 13 ATEX 0036X | |
| UL approval | E106378 | |
| IECEx approval | EXA 13.0003X | |
| Approved for | Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 2 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
| Power consumption | 2.2 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital output | ||
| Number of channels | 8 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 2- channel II: 3+, 4- channel III: 5+, 6- channel IV: 7+, 8- channel V: 9+, 10- channel VI: 11+, 12- channel VII: 13+, 14- channel VIII: 15+, 16- | |
| Current limit | 8 mA | |
| Open loop voltage | 20 V | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Test current | 0.33 mA | |
| Short-circuit | < 300 &Omega | |
| Open-circuit | > 50 k&Omega | |
| Response time | 20 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault , communication error red flashing | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative humidity | 95 % non-condensing | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 750 g | |
| Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 97 ATEX 1074 U | |
| Marking | II 2 G Ex d [ib] IIC Gb II (2) D [Ex ib Db] IIIC | |
| Galvanic isolation | ||
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PTB 97 ATEX 1075 PTB 97 ATEX 1074 U | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 2 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 2.2 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital output | ||
| Number of channels | 8 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 2- channel II: 3+, 4- channel III: 5+, 6- channel IV: 7+, 8- channel V: 9+, 10- channel VI: 11+, 12- channel VII: 13+, 14- channel VIII: 15+, 16- | |
| Current limit | 8 mA | |
| Open loop voltage | 20 V | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Test current | 0.33 mA | |
| Short-circuit | < 300 &Omega | |
| Open-circuit | > 50 k&Omega | |
| Response time | 20 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault , communication error red flashing | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 160 g | |
| Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 03 ATEX 2042 | |
| Marking | II (2) G [Ex ib] IIC II (2) D [Ex ib] IIIC | |
| Output | ||
| Voltage | 28 V | |
| Current | 13.5 mA | |
| Power | 376 mW (characteristic curve rectangular type) | |
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X PTB 03 ATEX 2042 | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ib Gb] IIC T4 Gc [Ex ib Db] IIIC | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
| Power consumption | 0.6 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 1 | |
| Function | ||
| Function | Counter  | |
| Function [2] | frequency | |
| Function [3] | direction of rotation | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection | channel I: 1+, 2/3- direction: 4+, 5/6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | in frequency + counter mode: 12.5 ms otherwise 20 µs | |
| Operating frequency | 0 ... 400 Hz in frequency + counter mode ... 40 Hz | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative humidity | 95 % non-condensing | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 350 g | |
| Dimensions | 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 97 ATEX 1074 U | |
| Marking | II 2(1) G Ex d [ia Ga] IIC Gb II (1) D [Ex ia Da] IIIC | |
| Input | ||
| Voltage | 10.5 V | |
| Current | 23.3 mA | |
| Power | 61.2 mW (linear characteristic) | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PTB 97 ATEX 1075 PTB 97 ATEX 1074 U | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 0.6 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 1 | |
| Function | ||
| Function | Counter  | |
| Function [2] | frequency | |
| Function [3] | direction of rotation | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection [3] | active binary signal 24 V DC | |
| Connection | channel I: 1+, 2- direction: 4+, 5- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | in frequency + counter mode: 12.5 ms otherwise 20 µs | |
| Operating frequency | 0 ... 15 kHz in frequency + counter mode ... 40 Hz | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Status LED (1) red: line fault | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 90 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PTB 03 ATEX 2042 | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ic] IIC T4 Gc | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 660 V DC / 1000 V AC max. | |
| Operating current | 1600 A max. | |
| Mechanical specifications | ||
| Enclosure cover | detachable , optional hinges | |
| Cover fixing | Stainless steel hexagonal head screws | |
| Degree of protection | IP66 (IP67 with O-ring) | |
| Cable entry | see PDF data sheet | |
| Defined entry area | see PDF data sheet | |
| Material | ||
| Enclosure | Aluminum alloy | |
| Finish | painted grey | |
| Mass | see PDF data sheet | |
| Mounting | see PDF data sheet | |
| Ambient conditions | ||
| Ambient temperature | see PDF data sheet | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | ||
| Group, category, type of protection, temperature class | [Ex] II 2 GDEx d IIB+H2 Gb (EJB20 / 20 A in aluminum: Ex d IIB) Ex tb IIIC Db | |
| International approvals | ||
| IECEx approval | IECEx INE 14.0029X | |
| Conformity | ||
| Degree of protection | EN60529 | |
| General information | ||
| Ordering information | This Solution will be delivered completely configured and assembled ready for use. For configuration details please contact Customer Service. | |
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power Bus or terminals 1-, 2+ | |
| Rated voltage | 16.8 ... 31.2 V DC | |
| Power dissipation | 0.9 W | |
| Power consumption | 1.3 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 5+, 6, 7- | |
| Input signal | 0/4 ... 20 mA | |
| Open circuit voltage/short-circuit current | &le 22 V / 30 mA | |
| Input resistance | max. 50 &Omega | |
| Transmission range | linearity range: -1 ... 110 % | |
| Available voltage | 16 V at 20 mA | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 3-, 4+ | |
| Ripple | &le 10 mV eff | |
| Transfer characteristics | ||
| Accuracy | max. 0.1 % of full-scale value | |
| Influence of ambient temperature | < 100 ppm/K of full-scale value | |
| Rise time/fall time | &le 3.5 ms | |
| Indicators/settings | ||
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) | |
| Mass | approx. 70 g | |
| Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | DEMKO 16 ATEX 1750X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| International approvals | ||
| UL approval | E106378 | |
| IECEx approval | IECEx UL 16.0116X | |
| Approved for | Ex nA IIC T4 Gc | |
| Accessories | ||
| Optional accessories | power feed module S1SD-2PF Power Bus POWERBUS-SETL5.*** Power Bus POWERBUS-SETH5.*** cover for DIN mounting rail POWERBUS-COV.250 end cap POWERBUS-CAP | |
| General specifications | ||
|---|---|---|
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | 50 &Omega | |
| Series resistance | max. 56 &Omega | |
| Fuse rating | 100 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 | |
| Safe area connection | ||
| Connection | terminals 7, 8 | |
| Working voltage | ||
| Supply loop | max. 8.5 V | |
| Measurement loop | max. 6.5 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| General specifications | ||
|---|---|---|
| Type | AC version | |
| Electrical specifications | ||
| Nominal resistance | 10 &Omega | |
| Series resistance | max. 79 &Omega | |
| Fuse rating | 50 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | max. 8.8 V | |
| Measurement loop | max. 6.5 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 00 ATEX 7096 | |
| Marking | II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA II T4 [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0355 (cULus) | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| Описание оборудования | ||
|---|---|---|
| 2-line protection | ||
| General specifications | ||
|---|---|---|
| Number of protected signal lines | 2 | |
| Indicators/settings | ||
| Labeling | space for labeling at the front | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 70 g | |
| Dimensions | 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 inch) | |
| Mounting | on the KF module | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 02 ATEX 2044 | |
| Marking | II (1)G [Ex ia Ga] IIC | |
| Internal capacitance | negligible | |
| Internal inductance | 200 µH | |
| Certificate | PF 16 CERT 3908 X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| IECEx approval | ||
| IECEx certificate | IECEx BAS 12.0123 | |
| IECEx marking | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
| Standards | IEC 60079-0:2011 , IEC 60079-11:2011 | |
| General specifications | ||
|---|---|---|
| Distance | Transmitter "K3": 300 m (1000 ft) Transmitter "K4": 120 m (400 ft) Transmitter "K5": 200 m (650 ft), 62.5 µ multimode 400 m (1300 ft), 50.0 µ multimode | |
| Supply | ||
| Connection | Monitor: power, CAT5, fiber (LC) | |
| Power consumption | Main unit: 48 W max, 100 ... 240 VAC, 50 ... 60 Hz 20-30 VDC Transmitter "K3": PS2 power Transmitter "K4": 5 VDC @ 10 W, max Transmitter "K5": 5 VDC @ 10 W, max | |
| Indicators/operating means | ||
| Indicators | Transmitter "K3": video check LED Transmitter "K4": video check LED front panel - power Transmitter "K5": video check LED front panel - power | |
| Display | ||
| Screen diagonal | 15 inch (381 mm) | |
| Response time | Standard: 30 ms High-bright : 25 ms | |
| Resolution | 1024 x 768 | |
| Color depth | 24 bit (16.7 M) color | |
| Contrast | Standard: 800:1 High-bright: 700:1 | |
| Brightness | Standard: 350 cd/m2 (nits) High-bright: 1200 cd/m2 (nits) | |
| Reading angle | 160° in all directions | |
| Life span | back lamp life: 50,000 hrs typical half life | |
| Input devices | Transmitter "K3": VGA - HD15M/F 2 x PS2 (keyboard & mouse) 1 x RS232 (touchscreen) 1 x RJ45 (CAT5e/6) Transmitter "K4": 29-pin DVI-D 2 x USB Type B (keyboard, mouse/touchscreen) 1 x RS232 (touchscreen) 1 x RJ45 (CAT5e/6) Transmitter "K5": 29-pin DVI-D 1 x USB Type B (keyboard, mouse/touchscreen) 1 x RS232 (touchscreen) fiber optic (multimode) LC connectors | |
| Touchscreen | 5-wire resistive 5-wire hardened resistive | |
| Keyboard | touchpad , optical trackball (50 mm) , joystick | |
| Serial data | ||
| Baud rate | 19.2 KBd max | |
| Flow control | RTS, CTS, DTR, DSR | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 89/336/EEC | EN55022A, EN61000-6-2, EN61000-3-2, EN61000-3-3 | |
| Ambient conditions | ||
| Operating temperature | -20 ... 50 °C (-4 ... 122 °F) | |
| Storage temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Relative humidity | 0 ... 90% (noncondensing) | |
| Shock resistance | 30g, 11 ms, all axis | |
| Vibration resistance | 5 ... 100 Hz 1G, 12 m/s2 | |
| Mechanical specifications | ||
| Degree of protection | Type 4X ( stainless steel ) Type 4 ( painted steel ) IP66 | |
| Material | Main enclosure: painted black steel or 316L stainless steel Main enclosure (rear cover): 6062 anodized aluminum, marine grade | |
| Installation | 100 mm ( 3.9   inch ) VESA mount | |
| Mass | Main unit: 11.3 kg (25 lb) without keyboard 16.8 kg (37 lb) with keyboard Transmitter "K3": 1.3 kg (2.9 lbs) Transmitter "K4": 0.3 kg (0.7 lbs) Transmitter "K5": 0.3 kg (0.7 lbs) | |
| Dimensions | Main enclosure: 478 x 381 x 86 mm (18.8 x 15.0 x 3.4 inch), junction box adds 43 mm (1.7 inch) to depth Keyboard enclosure: 559 x 254 x 51 mm (22.0 x 10.0 x 2.0 inch) Transmitter "K3": 198 x 99 x 36 mm (7.8 x 3.9 x 1.4 inch) Transmitter "K4": 104 x 135 x 36 mm (4.1 x 5.3 x 1.4 inch) Transmitter "K5": 104 x 135 x 36 mm (4.1 x 5.3 x 1.4 inch) | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | ||
| Group, category, type of protection | II 3G Ex ic nA IIC T4 Gc | |
| International approvals | ||
| ETL Intertek | Class I, Div. 2 Groups A, B, C, D T4 | |
| Описание оборудования | ||
|---|---|---|
| NPT1/2 thread | ||
| Описание оборудования | ||
|---|---|---|
| Pressure relief vent for use with the Pepperl+Fuchs Bebco EPS® purge and pressurization systems | ||
| Описание оборудования | ||
|---|---|---|
| Pressure relief vent for use with the Pepperl+Fuchs Bebco EPS® purge and pressurization systems | ||
| Описание оборудования | ||
|---|---|---|
| Pressure relief vent for use with the Pepperl+Fuchs Bebco EPS® purge and pressurization systems | ||
| Описание оборудования | ||
|---|---|---|
| Pressure relief vent for use with the Pepperl+Fuchs Bebco EPS® purge and pressurization systems | ||
| Описание оборудования | ||
|---|---|---|
| Pressure relief vent for use with the Pepperl+Fuchs Bebco EPS® purge and pressurization systems | ||
| Описание оборудования | ||
|---|---|---|
| Ex pz purge system for Zone 2 and 22 | ||
| General specifications | ||
|---|---|---|
| Operating mode | fully automatic (FA) | |
| Number of volume exchanges | 4 ... 19 | |
| Hazardous environment | gas or dust | |
| Supply | ||
| Rated voltage | 90 ... 264 V AC, 48 ... 62 Hz ±10 %, single phase 20 ... 30 V DC | |
| Power consumption | 100 ... 240 V AC - 2.3 VA (without digital valve) 20 ... 30 V DC - 2.5 W (without digital valve) | |
| Electrical specifications | ||
| Fuse rating | AC: 2 A DC: 3.15 A | |
| Input | ||
| Input I | Temperature, up to 2 RTD's per unit | |
| Connection | Pt100, 2-wire-connection | |
| Input type | temperature input | |
| Input II | 1 Bypass | |
| Connection | passive contact (switch) | |
| Input type | mechanical contact | |
| Output | ||
| Output I | ||
| Connection | K1, terminals: K1/N0, K1/N0 | |
| Output type | enclosure power, (1) SPST | |
| Inrush current | 6 A | |
| Contact loading | 6 A @ 250 V AC , 30 V DC resistive load, 6 A @ 30 V DC | |
| Output II | ||
| Connection | K2, terminals: K2(NO, C, NC) | |
| Output type | alarm, (1) DPST | |
| Inrush current | 3 A | |
| Contact loading | 3 A @ 250 V AC , 30 V DC resistive load, 3 A @ 30 V DC | |
| Output III | ||
| Connection | digital valve, terminals SV | |
| Output type | (1) SPDT, powered contacts from supply 0.08 A @ 250 VAC 0.5 A @ 30 VDC | |
| Inrush current | 3 A | |
| Indicators/settings | ||
| LED indicator | Membrane Pad K1: Green - Contact K1 is energized K2: Amber - Contact K2 is energized SV1/encl press.: Blue for safe pressure, Amber for valve on Bypass: Amber when bypass is active PT100 error: Red when fault in PT100 sensor | |
| Pneumatic parameters | ||
| Protective gas supply | instrument grade air or inert gas | |
| Safe pressure | - gas 0.7 mbar (0.3" H2O) - dust 1.6 mbar (0.65" H2O) | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| Shock resistance | EN 60068-2 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 40 °C (-4 ... 104 °F) at T6 -20 ... 60 °C (-4 ... 140 °F) at T4 | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Vibration resistance | 5 ... 100 Hz , 1 g, 12 m/s2, all axes | |
| Impact resistance | 30 g, 11 ms, all axes | |
| Mechanical specifications | ||
| Connection type | High pressure port: 1/8" NPTF Low pressure port: 1/8" NPTF | |
| Cable gland | Wire size M12 diameter 3 - 6.5mm M20 diameter 10 - 14mm RTD/Bypass: (3) M12x1.5 K1, K2, SV1: 'P_C' (3) M20x1.5 | |
| Degree of protection | Type 4X, IP66 | |
| Material | Housing: 316 stainless steel Cable Gland: 316 stainless steel or Nickel Plated Brass Pressure Ports: 316 stainless steel Membrane Pad: Autotex F200XE O-ring: EPDM | |
| Mass | approx. 2.7 kg (6 lb) | |
| Dimensions | 165 x 124 x 90 mm (6.5 x 4.9 x 3.5 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | ||
| Marking | external II 3 G Ex ic nA nC [ic pz IIC Gc] IIC T4 [Gc] (-20°C to 60°C) II 3 G Ex ic nA nC [ic pz IIC Gc] IIC T6 [Gc] (-20°C to 40°C) II 3 D Ex ic tc [ic pD IIIC Dc] IIIB T80°C Dc (-20°C to 60°C) II 3 D Ex ic tc [ic pD IIIC Dc] IIIB T60°C Dc (-20°C to 40°C) internal II 3 G Ex ic nA nC [ic pz IIC] IIC T4 [Gc] (-20°C to 60°C) II 3 G Ex ic nA nC [ic pz IIC] IIC T6 [Gc] (-20°C to 40°C) II 3 D Ex ic tc [ic pD IIIC Dc] IIIC T80°C Dc (-20°C to 60°C) II 3 D Ex ic tc [ic pD IIIC Dc] IIIC T60°C Dc (-20°C to 40°C) | |
| Directive conformity | ||
| Directive 94/9/EC | EN 60079-0:2012+A11:2013 , EN 60079-2:2007 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-31:2009 , EN 61241-4:2006 | |
| International approvals | ||
| UL approval | ||
| cULus | Class I Division 2 Group A-D T4 (-20°C to 60°C) Class I Division 2 Group A-D T6 (-20°C to 40°C) Class II Division 2 Group F+G T4 (-20°C to 60°C) Class II Division 2 Group F+G T6 (-20°C to 40°C) | |
| IECEx approval | Ex ic nA nC [ic pz IIC Gc] IIC T4 Gc (-20 °C to 60 °C) Ex ic nA nC [ic pz IIC Gc] IIC T6 Gc (-20 °C to 40 °C) Ex ic tc [ic pD IIIC Dc] IIIB T80°C Dc (-20 °C to 60 °C) External version Ex ic tc [ic pD IIIC Dc] IIIB T60°C Dc (-20 °C to 40 °C) External version Ex ic tc [ic pD IIIC Dc] IIIC T80°C Dc (-20 °C to 60 °C) Internal version Ex ic tc [ic pD IIIC Dc] IIIC T60°C Dc (-20 °C to 40 °C) Internal version | |
| General specifications | ||
|---|---|---|
| Operating mode | fully automatic (FA) | |
| Number of volume exchanges | 4 ... 19 | |
| Hazardous environment | gas or dust | |
| Supply | ||
| Rated voltage | 90 ... 264 V AC, 48 ... 62 Hz ±10 %, single phase 20 ... 30 V DC | |
| Power consumption | 100 ... 240 V AC - 2.3 VA (without digital valve) 20 ... 30 V DC - 2.5 W (without digital valve) | |
| Electrical specifications | ||
| Fuse rating | AC: 2 A DC: 3.15 A | |
| Input | ||
| Input I | Temperature, up to 2 RTD's per unit | |
| Connection | Pt100, 2-wire-connection | |
| Input type | temperature input | |
| Input II | 1 Bypass | |
| Connection | passive contact (switch) | |
| Input type | mechanical contact | |
| Output | ||
| Output I | ||
| Connection | K1, terminals: K1/N0, K1/N0 | |
| Output type | enclosure power, (1) SPST | |
| Inrush current | 6 A | |
| Contact loading | 6 A @ 250 V AC , 30 V DC resistive load, 6 A @ 30 V DC | |
| Output II | ||
| Connection | K2, terminals: K2(NO, C, NC) | |
| Output type | alarm, (1) DPST | |
| Inrush current | 3 A | |
| Contact loading | 3 A @ 250 V AC , 30 V DC resistive load, 3 A @ 30 V DC | |
| Output III | ||
| Connection | digital valve, terminals SV | |
| Output type | (1) SPDT, powered contacts from supply 0.08 A @ 250 VAC 0.5 A @ 30 VDC | |
| Inrush current | 3 A | |
| Indicators/settings | ||
| LED indicator | Membrane Pad K1: Green - Contact K1 is energized K2: Amber - Contact K2 is energized SV1/encl press.: Blue for safe pressure, Amber for valve on Bypass: Amber when bypass is active PT100 error: Red when fault in PT100 sensor | |
| Pneumatic parameters | ||
| Protective gas supply | instrument grade air or inert gas | |
| Safe pressure | - gas 0.7 mbar (0.3" H2O) - dust 1.6 mbar (0.65" H2O) | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| Shock resistance | EN 60068-2 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 40 °C (-4 ... 104 °F) at T6 -20 ... 60 °C (-4 ... 140 °F) at T4 | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Vibration resistance | 5 ... 100 Hz , 1 g, 12 m/s2, all axes | |
| Impact resistance | 30 g, 11 ms, all axes | |
| Mechanical specifications | ||
| Connection type | High pressure port: 1/8" NPTF Low pressure port: 1/8" NPTF | |
| Cable gland | Wire size M12 diameter 3 - 6.5mm M20 diameter 10 - 14mm RTD/Bypass: (3) M12x1.5 K1, K2, SV1: 'P_C' (3) M20x1.5 | |
| Degree of protection | Type 4X, IP66 | |
| Material | Housing: 316 stainless steel Cable Gland: 316 stainless steel or Nickel Plated Brass Pressure Ports: 316 stainless steel Membrane Pad: Autotex F200XE O-ring: EPDM | |
| Mass | approx. 2.7 kg (6 lb) | |
| Dimensions | 165 x 124 x 90 mm (6.5 x 4.9 x 3.5 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | ||
| Marking | external II 3 G Ex ic nA nC [ic pz IIC Gc] IIC T4 [Gc] (-20°C to 60°C) II 3 G Ex ic nA nC [ic pz IIC Gc] IIC T6 [Gc] (-20°C to 40°C) II 3 D Ex ic tc [ic pD IIIC Dc] IIIB T80°C Dc (-20°C to 60°C) II 3 D Ex ic tc [ic pD IIIC Dc] IIIB T60°C Dc (-20°C to 40°C) internal II 3 G Ex ic nA nC [ic pz IIC] IIC T4 [Gc] (-20°C to 60°C) II 3 G Ex ic nA nC [ic pz IIC] IIC T6 [Gc] (-20°C to 40°C) II 3 D Ex ic tc [ic pD IIIC Dc] IIIC T80°C Dc (-20°C to 60°C) II 3 D Ex ic tc [ic pD IIIC Dc] IIIC T60°C Dc (-20°C to 40°C) | |
| Directive conformity | ||
| Directive 94/9/EC | EN 60079-0:2012+A11:2013 , EN 60079-2:2007 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-31:2009 , EN 61241-4:2006 | |
| International approvals | ||
| UL approval | ||
| cULus | Class I Division 2 Group A-D T4 (-20°C to 60°C) Class I Division 2 Group A-D T6 (-20°C to 40°C) Class II Division 2 Group F+G T4 (-20°C to 60°C) Class II Division 2 Group F+G T6 (-20°C to 40°C) | |
| IECEx approval | Ex ic nA nC [ic pz IIC Gc] IIC T4 Gc (-20 °C to 60 °C) Ex ic nA nC [ic pz IIC Gc] IIC T6 Gc (-20 °C to 40 °C) Ex ic tc [ic pD IIIC Dc] IIIB T80°C Dc (-20 °C to 60 °C) External version Ex ic tc [ic pD IIIC Dc] IIIB T60°C Dc (-20 °C to 40 °C) External version Ex ic tc [ic pD IIIC Dc] IIIC T80°C Dc (-20 °C to 60 °C) Internal version Ex ic tc [ic pD IIIC Dc] IIIC T60°C Dc (-20 °C to 40 °C) Internal version | |
| Описание оборудования | ||
|---|---|---|
| Pressure relief vent | ||
| Описание оборудования | ||
|---|---|---|
| Pressure relief vent | ||
| Описание оборудования | ||
|---|---|---|
| Type X & Ex px purge and pressurization system | ||
| Описание оборудования | ||
|---|---|---|
| Type X & Ex px purge and pressurization system | ||
| Описание оборудования | ||
|---|---|---|
| Type Ex px purge and pressurization system | ||
| General specifications | ||
|---|---|---|
| Distance | Transmitter "K3": 300 m (1000 ft) Transmitter "K4": 120 m (400 ft) Transmitter "K5": 200 m (650 ft), 62.5 µ multimode 400 m (1300 ft), 50.0 µ multimode | |
| Supply | ||
| Connection | Monitor: power, CAT5, fiber (LC) | |
| Power consumption | Main unit: 70 W max, 100 ... 240 VAC, 50 ... 60 Hz 20-30 VDC Transmitter "K3": PS2 power Transmitter "K4": 5 VDC @ 10 W, max Transmitter "K5": 5 VDC @ 10 W, max | |
| Indicators/operating means | ||
| Indicators | Transmitter "K3": video check LED Transmitter "K4": video check LED front panel - power Transmitter "K5": video check LED front panel - power | |
| Display | ||
| Screen diagonal | 19 inch (483 mm) | |
| Response time | Standard: 12 ms High-bright: 5 ms | |
| Resolution | 1280 x 1024 | |
| Color depth | 24 bit (16.7 M) color | |
| Contrast | 1000:1 | |
| Brightness | Standard: 450 cd/m2 (nits) High-bright: 1000 cd/m2 (nits) | |
| Reading angle | 160° in all directions | |
| Life span | back lamp life: 50,000 hrs typical half life | |
| Input devices | Transmitter "K3": VGA - HD15M/F 2 x PS2 (keyboard & mouse) 1 x RS232 (touchscreen) 1 x RJ45 (CAT5e/6) Transmitter "K4": 29-pin DVI-D 2 x USB Type A (keyboard, mouse/touchscreen) 1 x RS232 (touchscreen) 1 x RJ45 (CAT5e/6) Transmitter "K5": 29-pin DVI-D 2 x USB Type A (keyboard, mouse/touchscreen) 1 x RS232 (touchscreen) fiber optic (multimode) LC connectors | |
| Touchscreen | 5-wire resistive 5-wire hardened resistive | |
| Serial data | ||
| Baud rate | 19.2 KBd max | |
| Flow control | RTS, CTS, DTR, DSR | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 89/336/EEC | EN55022A, EN61000-6-2, EN61000-3-2, EN61000-3-3 (main unit) EN55022, EN55024, IEC61000-4-2, IEC61000-4-3, IEC61000-4.4, IEC61000-4-5, EN61000-3-2, EN61000-3-3 (KVM transmitters) | |
| Low voltage | ||
| Directive 73/23/EEC | EN60950 (KVM transmitters) | |
| Ambient conditions | ||
| Operating temperature | -20 ... 50 °C (-4 ... 122 °F) | |
| Storage temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Relative humidity | 0 ... 90% (noncondensing) | |
| Mechanical specifications | ||
| Degree of protection | Nema Type 4X | |
| Material | 304 (UNS S30400) stainless steel | |
| Mass | approx. 52.16 kg (115 lbs) Empty housing Varies with configuration | |
| Dimensions | 813 x 724 x 381 mm (32.0 x 28.5 x 15.0 inch) (sloping top) Volume: approx. 3.2 cu ft | |
| International approvals | ||
| UL approval | cULus | |
| Approved for | Class I, Division 1, Group A, B, C, D | |
| Описание оборудования | ||
|---|---|---|
| 10 inch flat panel monitor for Class I, Div 2 applications. | ||
Товаров: 0